7.5.- Pump down function 

This function prevents compressor problems caused by movement of the refrigerant, using a stop/start technique of 
the unit controlled by liquid solenoid, the low pressure switch and the compressor.
For this function to be active, it must be configured in parameter 

P26= 1.

PARO

When the temperature in probe 1 reaches the set point (

SP

) value, the liquid solenoid closes.

Since the compressor is still running the evaporator pressure drops suddenly. When it reaches a specific point, the 
low pressure switch is activated, changing the state of digital input 1, and the controller stops the compressor.
This manoeuvre isolates the refrigerant from the compressor crankcase, preventing serious damage on start-up.
In case of low pressure switch failure, the controller stops the compressor after the safety time set at 

P15,

 showing 

the message "

Pd

", but it will continue to function normally. (informative message, does not affect the equipment 

operation).
If time 

P15

 is 0 (default value), the compressor will not stop until the low pressostat is activated, but it will display 

the “

Pd

” message after 15 minutes.

STARTUP

When the temperature in probe 1 reaches the set point plus the differential (

SP

 + 

C1

) value, the liquid solenoid 

opens.  This  increases  the  pressure  in  the  evaporator,  deactivating  the  low  pressure  switch,  which  turns  the 
compressor on.
If a period of time (determined by 

P14

) has elapsed after the liquid solenoid is opened, the low pressure switch 

will not be deactivated, the controller will once again close the solenoid, and the “

LP

” message will be displayed. 

This  manoeuvre  will  be  repeated  every  2  minutes,  indefinitely,  until  the  pressure  switch  is  deactivated  and  the 
installation reverts to its normal operation.
If the time for 

P14

 is 0 (default value), the solenoid will stay open until the low pressure switch is deactivated, but 

after 3 minutes it will display the “

LP

” message.

STAND-BY

If  the  pump-down  function  is  active,  some  time  may  elapse  from  the  time  the  stand-by  function  starts  until  the 
controller stops. This is because certain control phases of the system cannot be stopped.

ON

Liquid 

solenoid

Low pressure 

switch

Pressure 
switch fault

Pressure 
switch fault

Compressor

Evaporator 

pressure

ON

ON

+

P15

P14

OFF

OFF

OFF

SOLEN.

Digital

Input

COMP.

Time

SP

SP

SP+C1

SP+C1

13

Содержание PROCool AKO-17635-1

Страница 1: ...AKO 17635 1 AKO 17635 2 PROCool Electronic Panel GB 1763H532 Ed 02 User manual 1...

Страница 2: ...damage which may occur due to failure to comply with these regulations Rigorouslyfollowtheinstructionsdescribedinthismanual Inordertoextendthelifetimeofourproductstothemaximum thefollowingpointsmustbe...

Страница 3: ...only probes supplied by AKO should be used Between 40 C and 20 C if the NTC probe is extended up to 1 000 m with minimum 0 5 mm wire the maximum deviation will be 0 25 C Wire for probe extension ref...

Страница 4: ...Checks before starting the panel up Powersupplyvoltagesandfrequencieswillbetheonesthatfigureinthe Technicalspecifications section Checkthattherearenoloosepartsorforeignbodiesonconnectionsorswitchgear...

Страница 5: ...the advanced configurationmenu During configuration it allows you to scroll through the different levels or when setting a parameter tochangeitsvalue One short press displays the current set point va...

Страница 6: ...ture set in A2 has been reached p 14 Alternating with temperature External alarm activated by digital input p 14 Alternating with temperature Severe external alarm activated by digital input p 14 Alte...

Страница 7: ...escribed depends on the panel model AKO 17635 1 AKO 17635 2 Identification F1 General circuit breaker FM Operation circuit breaker FK1 Compressor motor guard condenser fan 1 depending on model K1M Com...

Страница 8: ...1 Maximum defrost duration The defrost will end after this time has elapsed since it started F3 Fan status during defrost It defines the status of the fans during defrost 0 Stopped 1 Running A1 Maximu...

Страница 9: ...n external switch configuring one of the digital inputs as Change set point P10 or P11 4 If we set the C11 parameter to 0 it can only be activated by external switch ON SP SP Dif OFF COMP C When the t...

Страница 10: ...he average performance of the last 24 hours taking into account the number of starts and stops and the average time in each state stop start C6 3 The compressor will run as scheduled in C7 ON and C8 O...

Страница 11: ...mination The defrost will terminate if The temperature programmed in parameter d4 has been reached in probe 2 Probe 2 must be activated P4 In the event of probe 2 failure defrosting will be complete o...

Страница 12: ...configuredas remotedefrost P10 P11 6 7 3 Fan control Fans are controlled with probe 2 evaporator and parameters F0 shutdown temperature and F1 Probe differential Even if probe 2 is not connected or an...

Страница 13: ...sostat is activated but it will display the Pd message after 15 minutes STARTUP When the temperature in probe 1 reaches the set point plus the differential SP C1 value the liquid solenoid opens This i...

Страница 14: ...nd is disabled when it reaches 8 degrees In the case of configuring the alarms in relation to the SP A0 0 the value set for the SP parameter is taken as a reference even though the CHANGE SET POINT fu...

Страница 15: ...er defrost A4 Delays activation of temperature alarms post defrost Delay of max min temperature alarm A5 Delays activation of maximum A1 and minimum A2 temperature alarms from the moment temperature p...

Страница 16: ...ipment to the key Connect the programming key in the parameter server connector Press the READ key on the programming key Disconnect the device programming key Transfer parameters from the key to the...

Страница 17: ...isfunctionconfiguresalltheunit sparameterstoitsdefaultvalues i e asitleavesthefactory In order to return the computer to its initial settings go to the programming menu and set parameter P3 to 1 The c...

Страница 18: ...45 C2 C4 Typeofdelayforprotectionofthecompressor Page10 0 OFF ON sincethelastdisconnection 1 OFF ON ON OFF sincethelastshut down start up 0 0 1 C5 Protectiondelaytime valueoftheoptionselectedinparame...

Страница 19: ...up Page12 0 NO Firstdefrostasperd0 1 YES Firstdefrostasperd6 0 0 1 d6 Defroststartdelayonequipmentstart up Page12 min 0 0 255 d8 Calculatedtimebetweendefrostperiod Page12 0 Totalactualtime 1 Sumoftim...

Страница 20: ...nalofthedigitalinputdisappears P10orP11 2or3 Page15 min 0 0 120 A8 Showwarningifdefrostisterminatedbytime out 0 No 1 Yes Page14 0 0 1 A10 TemperatureAlarmDifferential A1andA2 Page14 C F 0 1 1 0 20 0 A...

Страница 21: ...mumstart uptimeafterpumpdown Page13 Valuesbetween1and9secondsarenotaccepted 0 Disabled sec 0 0 120 P15 Maximumpumpdowntime Page13 0 Disabled min 0 0 15 P23 Stopevaporatorfansandcompressoronopeningdoor...

Страница 22: ...ion 1 C PrecisionoftheNTCprobeat25 C 0 4 C InputforNTCprobe AKO 14901 Maximuminputpowerintheoperation 30VA Workingambienttemperature 5 Cto40 C Storageambienttemperature 30 Cto70 C Overvoltagecategory...

Страница 23: ...ight to supply materials that might vary slightly to those described in ourTechnical Sheets Updated information is available on our website AKO ELECTROMEC NICA S A L Avda Roquetes 30 38 08812 Sant Per...

Отзывы: