3516526A11 Ed. 02
33
Basic configuration
Level 1
Level 2
Description
Values Min. Def. Max.
bcn
b00
Delay of all functions on receiving power supply
min.
0
0
255
b01
Cold room light timing
min.
0
0
999
b10
Password function 0=Inactive 1=Block access to parameters 2=Lock keypad
0
0
2
PAS
Password
0
0
99
b20
MODBUS address
1
1
247
b21
Communication speed: 0=9600 bps 1=19200 bps 2=38400 bps
3=57600 bps
bps
0
0
3
b22
Audible alarm enabled 0= No 1=Yes
0
1
1
b23
Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor S5, 5=Su-
perheating, 6=Pressure sensor, 7=% EEV, 9=Carousel, 10 = Off
1
*
10
b30
Activation of manual calibration 0=Deactivated
1= Activated Requires security code
0
0
1
Unt
Working units 0=ºC 1=ºF
0
0
1
EP
Output to level 1
Inputs and outputs
Level 1
Level 2
Description
Values Min. Def. Max.
InO
I00
Probes connected: 1=Sensor 1 (cold room), 2=Sensor 1 (cold room) + Sensor
2 (evaporator)
1
2
2
I10
D1 / S3 input configuration: 0=Deactivated, 1=Door contact, 2=External
alarm, 3=Severe external alarm, 4=Change SP, 5=Remote defrost, 6=Defrost
lockout, 7=Low pressure switch, 8=Remote activation in standby mode,
9=Product temperature
0
*
9
I11
Digital input polarity D1: 0=Activates on closing, 1=Activates on opening
contact
0
0
1
I20
D2 / S4 input configuration: 0=Deactivated, 1=Door contact, 2=External
alarm, 3=Severe external alarm, 4=Change SP, 5=Remote defrost,
6=Defrost lockout, 7=High pressure switch for hot gas, 8=Remote activation
of standby mode, 9=Product temperature, 10=Defrost 2nd evaporator,
11=2nd cold room temperature probe
0
*
11
I21
Digital input polarity D2: 0=Activates on closing, 1=Activates on opening
contact
0
0
1
I60
Pressure units: 0= bar, 1= Psi
0
*
1
I61
Pressure sensor type (S6): 0= Deactivated, 1= 4-20 mA, 2= 0-5 V,
3= 0.5-4.5 V, 4= 0-10 V, 5= 1-5 V
0
0
5
I62
Minimum pressure sensor value (4mA, 0V, 0.5V, 1)
-1
0
I63
I63
Maximum pressure sensor value (20mA, 5V, 4.5V, 10V)
I62 12
60
I64
Pressure sensor calibration (S2)
-10
0
10
* According to the set-up wizard.