3516526A11 Ed. 02
26
Calibration ongoing, therefore, avoid, as far as possible, opening the cold room during
the process.
Flashing light with temperature: Configuration has been changed from 1 to 2 evaporators
or vice versa.
Excessive door openings have been detected during calibration and it has not been pos-
sible to calibrate.
Excessive door openings have been detected and the device cannot regulate in SELFDRIVE
mode.
Defrost end error in 1/2 evaporator during the calibration, defrost has not
ended due to temperature.
Error during calibration in 1/2 evaporator. There is not enough difference in
temperature between the cold room probe and the evaporator probe.
It has not been possible to carry out the calibration due to a lack of stability
in the system (Excessive door opening, excessive oscillations in the lower
pressure, etc.).
Error during normal operation (SELFDRIVE Mode active) in 1/2 evaporator.
There is not enough difference in temperature between the cold room probe
and the evaporator probe.
A lack of stability has been detected in the system (Excessive door open-
ing, excessive oscillations in the low pressure, etc.) during normal operation
(SELFDRIVE Mode active).
The persistent lack of stability has led to the deactivation of the SELFDRIVE
mode.
SELFDRIVE mode alert messages
(Only shown by pressing the
key)