3516526A11 Ed. 02
22
Assistant
The first time the unit receives the power supply, it will enter into ASSISTANT
mode. The display will show the message
In{
flashing at
0
.
The buttons
and
change the value, the
SET
button accepts the
value and moves on to the next step.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press
SET
.
The available options will be shown in the following table:
InI
Type of installation
Parameters
Control of
the compressor
Pump
Down
Defrost
Vent.
Evap.
Pd o00 o20 I00 I10 I11 I20 I21 d1 D7 F3
0
Demo mode: it displays the temperature but does not regulate the temperature
1
No
No
Electric
Yes
0
0
*
2
0
0
0
0 20 0
0
2
Yes
Yes
Electric
Yes
1
1
*
2
7
1
0
0 20 0
0
3
Yes
No
Electric
Yes
0
1
*
2
0
0
0
0 20 0
0
4
No
No
Air
Yes
0
0
*
1
0
0
0
0 20 1
1
5
Yes
Yes
Air
Yes
1
1
*
1
7
1
0
0 20 1
1
6
Yes
No
Air
Yes
0
1
*
1
0
0
0
0 20 1
1
7
Yes
Yes
Hot gas
Yes
1
1
*
2
7
1
7
1
5
2
0
8
Yes
No
Hot gas
Yes
0
1
*
2
0
0
7
1
5
2
0
* If
u00
=2:
o20
=3
If
u00
≠
2:
o20
=0
If options 2, 5 or 7 are chosen, check the configuration of parameter I11 according to the pressure switch
type used.
Step 2:
Choose the type of expansion valve to be used:
u00=1
PWM-controlled solenoid valve
u00=2
Electronic expansion valve (Requires an external controller for
the EEV. For more information, please refer to the
available on our website)
If u00=2 is chosen, step 3 is not displayed.
1
/
/ SET
2
/
/ SET