1652H4A02 Ed.09
38
Troubleshooting
Errors during calibration
The error message is displayed alternately with the CAL message. The
icon flashes.
Error
Description
Solution
E1/E2/E3
Probe error 1 / 2 / 3
Check condition and wiring of affected probe
E10
Evaporator defrost error
Check defrost operation, it must end by
temperature (d4)
E20
Idem for E10 but relating to the second evaporator
E11
Similar temperature in probes S1 and S2
Check position of both probes following
recommendations on page 8
E20
Idem for E11 but relating to probe S3
E12
It has not been possible to carry out the calibration
due to a lack of stability in the system
Avoid opening cold room door during calibration.
Check main components of the refrigeration
circuit, in particular the aspiration part
E22
Idem for E12 but relating to the second evaporator
E17
Excessive door openings have been detected
during calibration and it has not been possible to
calibrate.
Avoid opening cold room door during calibration.
Error
Description
Solution
E1/E2/E3
Probe error 1 / 2 / 3
Check condition and wiring of affected probe
E13
Similar temperature in probes S1 and S2
Check position of both probes following
recommendations on page 8
E23
Idem for E11 but relating to probe S3
E14
A lack of stability has been detected in the system Check main components of the refrigeration
circuit, in particular the aspiration part
E24
Idem for E14 but relating to the second evaporator
E15
Persistent lack of system stability has led to
deactivation of the SELFDRIVE mode
Check main components of the refrigeration
circuit, in particular the aspiration part and the
position of probe 2 or 3.
To return to the SELFDRIVE mode restart the
device
E25
Idem for E15 but relating to the second evaporator
E16
Configuration has been changed from 1 to 2
evaporators or vice versa.
If the configuration change is correct, start a
manual calibration
E18
Excessive door openings have been detected and
the device cannot regulate in SELFDRIVE mode.
Check that the door has not been left open or
that it does not open more than necessary
Errors during operation
The error message is displayed alternately with the temperature. The
icon flashes.