1652H4A02 Ed.09
30
Configuration
Condensed programming menu
This allows for the most-used parameters to be quickly configured. Press the
SET
key for 3 seconds to access it.
Parameters
Condensed programming menu
Parameters
Change
parameter
Values
Save changes
Do not save changes
OK
20 sec.
20 sec.
OK
OK
Change
value
Temperature
indication
3 seg.
OUT OF
PROGRAMMING
IN PROGRAMMING
Description
Values Min.
Def.
Max.
SP
Temperature setting (Set Point)
ºC/ºF
-50
0.0
99
CE
SELFDRIVE Mode
0
=Deactivated
1
= Activated
0
1
1
C1
Probe 1 differential (Hysteresis)
ºC/ºF
0.1
2.0
20.0
d0
Defrost frequency (Time between 2 starts)
H.
0
6
96
d1
Maximum defrost duration (
0
=defrost deactivated)
Min.
0
*
255
d4
Final defrost temperature (by probe) (If P4
¹
1)
ºC/ºF
-50
8.0
50
F3
Status of the fans during the defrost
0
=Shut down;
1
=Running
0
0
1
A1
Alarm for maximum in probe 1 (It should be higher than the SP)
ºC/ºF
A2
99
99
A2
Alarm for minimum in probe 1 (It should be lower than the SP)
ºC/ºF
-50
-50
A1
d30
Defrost strategy in SELFDRIVE mode
0
5
10
Level 2
* According to wizard.