10
Initial configuration (wizard)
The first time the unit receives the power supply, it will enter into
ASSISTANT mode. The display will show the message
In{
flashing at
0
.
Step 1:
Select the most suitable InI option based on the type of installation to be
carried
out and press
SET
. The available options will be shown in the
following table:
If options 2, 5, or 7 are chosen, check the configuration of parameter I11 according to the pressure
switch type used. (See diagram included with the device).
Step 2:
Use keys
N
and
Q
to enter the desired Set Point value and press
SET
.
The configuration wizard has finished. The unit will begin to regulate the
temperature.
If this is not the first time you run the wizard, after completing the last
step the display will show the message
dFp
(default parameters). You
may choose between two options:
0:
Only change the parameters which affect the wizard. The other
parameters will remain the same.
1:
All parameters return to their factory setting except those
which have been modified by the wizard.
The co
nfiguration wizard will not reactivate. To reactivate it, activate the Stand-By mode (by pressing the
m
key for 3 seconds) and wait until the unit completely halts regulation (the
m
indicator will light up
permanently) and press in this order the following keys (one after the other, not at the same time)
N
,
Q
and
SET
.
STAND-BY
If the regulation cannot be instantly stopped due to its configuration, a controlled stop process starts
and the
m
icon flashes. To stop the controlled stop process and force the step to Stand-by, press the
Stand-by key again for 3 seconds.
In{
Type of installation
Parameters
Diagram
to be
used
Cold
regulation
Pump
Down
Defrost
Evaporator
fans
Pd o00 I00 I10 I11 I20 I21 d1 d7 F3
0
Demo mode: it displays the temperature but does not regulate the temperature or activate relays.
1
Solenoid
No
Electric
Yes
0
*
2
0
0
0
0
20
0
0
A
2
So compressor
Yes
Electric
Yes
1
1
2
7
1
0
0
20
0
0
B
3
So compressor
No
Electric
Yes
0
1
2
0
0
0
0
20
0
0
B
4
Solenoid
No
Air
Yes
0
*
1
0
0
0
0
20
1
1
A
5
So compressor
Yes
Air
Yes
1
1
1
7
1
0
0
20
1
1
B
6
So compressor
No
Air
Yes
0
1
1
0
0
0
0
20
1
1
B
7
So compressor
Yes
Hot gas
Yes
1
1
2
7
1
9
1
5
2
0
C
8
So compressor
No
Hot gas
Yes
0
1
2
0
0
9
1
5
2
0
C
*
o00
=2 in AKO-16523 / 16520,
o00
=0 in AKO-16523P / 16520P / 16523D.
CORE
CORE
CORE
CORE
CORE
CORE
CORE
CORE
1
2
1652H4A02 Ed.09