1652H302 Ed.03
25
Description
Values Min.
Def.
Max.
fAN
F0
Shutdown temperature of fans
ºC/ºF
-50
45
50
F1
Probe 2 differential if fans are shut down
ºC/ºF
0.1
2.0
20.0
F2
Shut down fans when the compressor shuts down
0
=No
1
=Yes
0
0
1
F3
Status of the fans during the defrost
0
=Shut down;
1
=Running
0
0
1
F4
Delay of start-up after defrost (If F3=0)
It will only actuate if it is higher than
d9
Min.
0
2
99
EP
Exit to level 1
Description
Values Min.
Def.
Max.
DEF
d0
Defrost frequency (Time between 2 starts)
H.
0
6
96
d1
Maximum defrost duration (
0
=defrost deactivated)
Min.
0
*
255
d2
Type of message during the defrost:
0
=Displays the real temperature;
1
=Displays the temperature at the start of the
defrost;
2
=Displays the dEF message
0
2
2
d3
Maximum duration of the message
(Time added at the end of the defrost process)
Min.
0
5
255
d4
Final defrost temperature (by probe) (If P4
¹
1)
ºC/ºF
-50
8.0
C2
d5
Defrost on connecting the unit:
0
=NO First defrost according to d0;
1
=YES, First defrost according to d6
0
0
1
d6
Delay of the defrost start on connecting the unit
Min.
0
0
255
d7
Type of defrost:
0
=Resistors;
1
=Air/fans
2
=Hot gas;
3
=Reversal of cycle
0
*
3
d8
Count of time between defrost periods:
0
=Total real time
1
=Sum of compressor connected time
0
0
1
d9
Drip time when completing defrost (Shutdown of compressor and fans)
Min.
0
1
255
EP
Exit to level 1
Level 1
Level 1
Level 2
Level 2
Defrost
Evaporator fans
†
* According to wizard.
It can only be modified using the configuration wizard (InI).
†