17
Other parameters
Using parameter
d5
, you can configure whether the unit performs a defrost (
d5
=1) or not (
d5
=0) when it receives
power (first start-up or after a power supply failure). Should the option YES (
d5
=1) be selected, defrost will begin
once the delay time defined in
d6
has elapsed.
Using parameter
d8
, we define the time tally established in
d0
, choosing between total time elapsed (
d8
=0) or
the sum of compressor operation time (
d8
=1).
REMARK:
If parameter
d1
is configured to 0, no defrosts are performed.
Fan control
Fans are controlled through probe 2 (evaporator) and parameters
F0
(stop temperature) and
F1
(probe differential).
If probe 2 is not connected or an error in the probe (
E2
) is detected, the fans continuously operate without taking
into account parameters
F0
and
F1
, but taking the remaining parameters (
F2
to
F4
) into account.
Using parameter
F2
, the status of the fans during compressor stops is defined.
Using parameter
F3
, the status of the fans during defrost is defined.
Parameter
F4
defines the fan start-up delay time after defrost (see p. 15).
Parameter
C22
defines whether fans stop when the door is opened.
SP
SP
F0
S2
F0-F1
Fans
COOL
ON
ON
ON
ON
ON
SP+C1
F2
=1
F2
=0
1652H302 Ed.03