1652H302 Ed.03
27
* According to wizard.
** Option not available in
AKO-16523 / 16520
It can only be modified using the configuration wizard (InI).
†
Description
Values Min.
Def.
Max.
In0
I00
Connected probes
1
=Probe 1 (Cold room)
2
=Probe 1 (Cold room) + Probe 2 (Evaporator)
1
2
2
I10
Configuration of digital input 1
0
= Deactivated
1
=Door contact
2
=External alarm
3
=Severe external alarm
4
=Change of SP
5
=Remote defrost
6
=Defrost block
7
= Low pressure switch
0
*
7
I11
Polarity of the digital input 1
0
=Activates on closing contact;
1
=Activates on opening contact
0
*
1
I20
Configuration of digital input
2
0
= Deactivated
1
=Door contac
2
=
2
=External alarm
3
=Severe external alarm
4
=Change of SP
5
=Remote defrost
6
=Defrost block
7
=Register probe
8
=Probe 2° evaporator **
9
=High pressure switch for Hot Gas
0
0
9
I21
Polarity of the digital input 2
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
O00
Configuration of relay AUX1
0
=Deactivated
1
=Compressor/Resistor sump
2
=Light
3
=Virtual control
0
*
3
O10
Configuration of relay AUX2 (Not available in AKO-16523/16520)
0
=Deactivated
1
=Alarm
2
=Light
3
=Virtual control
4
=Door frame resistance
5
=Defrost 2° evaporator
6
=Same as solenoid status
7
=Same as unit status
0
2
7
EP
Exit to level 1
Level 1
Level 2
Inputs and outputs
Description
Values Min.
Def.
Max.
KCP
h1
Maximum temperature of HACCP alarm
ºC/ºF
-50
99
99
h2
Maximum permitted time for activation of the HACCP alarm (
0
=Disabled)
H.
0
0
255
EP
Exit to level 1
Level 1
Level 2
HACCP alarm
Description
Values Min.
Def.
Max.
TiD
IN{
Option chosen in the configuration wizard
Pd
Pump down active?
0
=No
1
=Yesi
PU
Programme version
Pr
Programme revision
EP
Exit to level 1
Level 1
Level 2
Information (Reading only)
†
†
†