CONTROL SYSTEM
12-4
SM PNXADCI 1-A.1 GB
‘D’:
(Night Mode Speed)
NightPercent
NA
‘E’:
-
End of Deicer
-
When Compressor changes to off (Ventilation)
-
OMT and OCT fault in heat mode
Off
On
‘F’:
-
Test Mode
Off
On
12.1.6.3 OFAN Operation
With keeping the OFAN general rules above in the highest priority, the operation of the OFAN will
be operating as the following:
Cooling
heating
•
The Triac and the Relay can never be activated at the same time
12.1.7
EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEV
OL
+ EEV
CV
•
EEV
OL
is the initial EEV opening as a function of the compressor frequency, operation mode,
unit model and capacity.
•
EEV
CV
is a correction value for the EEV opening that is based on the Target CTT and
discharge superhea.
•
During the first 5 minutes of compressor operation EEV
CV
= 0.
•
Once the first 5 minutes are over, the correction value is calculated as follow: EEV
CV
=
EEV
SH Discharge
+ EEV
Target CTT
•
EEV
SH Discharge
For cooling, SH
DischargeC
= CTT- OMT
For Heating, SH
DischargeH
= CTT- ICT
•
EEV
Target CTT
For cooling,
Target CTT
=
Target_CTT_Alpha_C
*OMT
-
Target_CTT_Beta_C
*ICT
+
Target_CTT_Gamma_C
*Actual Compressor Frequency
+
Target_CTT_Delta_C
For Heating,
Target CTT
=
Target_CTT_Alpha_H
*ICT
-
Target_CTT_Beta_H
*OCT
Содержание PNXA 12 DCI
Страница 16: ...4 3 OUTLINE DIMENSIONS SM PNXADCI 1 A 1 GB 4 5 Outdoor Unit YBD 024...
Страница 99: ...EXPLODED VIEW SPARE PART LIST 14 6 SM PNXADCI 1 A 1 GB 14 6 Exploded view of outdoor Unit GC 9 12 DCI...
Страница 101: ...EXPLODED VIEW SPARE PART LIST 14 8 SM PNXADCI 1 A 1 GB 14 8 Exploded view of outdoor Unit YBD018...
Страница 103: ...EXPLODED VIEW SPARE PART LIST 14 10 SM PNXADCI 1 A 1 GB 14 10 Exploded view of outdoor Unit YBD022...
Страница 105: ...EXPLODED VIEW SPARE PART LIST 14 12 SM PNXADCI 1 A 1 GB 14 12 Exploded view of outdoor Unit YBD024...
Страница 108: ...APPENDIX A SM PNXADCI 1 A 1 GB 16 1 APPENDIX A INSTALLATION AND OPERATION MANUALS...