CONTROL SYSTEM
SM PNXADCI 1-A.1 GB
12-11
12.7.10
Exceeding operation conditions
Exceeding limits state
Normal state
(
default
)
Outdoor conditions
EnableExceedCond
Indoor
Mode
request
Indoor
Hydro
(Family 31)
Indoor
Non Hydro
(Family is not 31)
1
0 (or OAT
faulty)
Outdoor mode
Cooling
A=47
A=47
Idle
Cooling
Cool
Cooling
B=-11
B=-11
Idle
Cooling
Cool
Heating
B=-18
B=-18
Idle
Heating
Heat
Heating
A=+40
A=+30
Idle
Heating
Heat
12.8
Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J8.
Function
Contact = Open
Contact = Short
J8 = Open
Presence Detector Connection No Limit
Forced to STBY
J8 = Short
Power Shedding Function
No Limit
Limit NLOAD
12.9
Operating the Unit from the Mode Button
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set
temperature according to the following table:
Forced operation Mode
Pre-set Temperature
Cooling
20
0
C
Heating
28
0
C
12.10
Indoor Unit Controllers and Indicators
STAND BY
INDICATOR
1.
Lights up when the Air Conditioner is connected to power
and ready to receive the R/C commands
OPERATION
INDICATOR
1.
Lights up during operation.
2.
Blinks for 300 msec., to announce that a R/C infrared
signal has been received and stored.
3.
Blinks continuously during protections (according to the
relevant spec section).
TIMER INDICATOR
Lights up during Timer and Sleep operation.
FILTER INDICATOR
Lights up when Air Filter needs to be cleaned.
COOLING INDICATOR
Lights up when system is switched to Cool Mode by using the
Mode Switch on the unit.
Содержание PNXA 12 DCI
Страница 16: ...4 3 OUTLINE DIMENSIONS SM PNXADCI 1 A 1 GB 4 5 Outdoor Unit YBD 024...
Страница 99: ...EXPLODED VIEW SPARE PART LIST 14 6 SM PNXADCI 1 A 1 GB 14 6 Exploded view of outdoor Unit GC 9 12 DCI...
Страница 101: ...EXPLODED VIEW SPARE PART LIST 14 8 SM PNXADCI 1 A 1 GB 14 8 Exploded view of outdoor Unit YBD018...
Страница 103: ...EXPLODED VIEW SPARE PART LIST 14 10 SM PNXADCI 1 A 1 GB 14 10 Exploded view of outdoor Unit YBD022...
Страница 105: ...EXPLODED VIEW SPARE PART LIST 14 12 SM PNXADCI 1 A 1 GB 14 12 Exploded view of outdoor Unit YBD024...
Страница 108: ...APPENDIX A SM PNXADCI 1 A 1 GB 16 1 APPENDIX A INSTALLATION AND OPERATION MANUALS...