11-7
CONTROL SYSTEM
SM PNXADCI 1-A.1 GB
11.7.5
Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST Trend
HST
Decreasing
No Change
Increasing
HST
SC
SC
SC
> 90
85 < HST
90
D1
D2
D2
82 < HST
85
SR
D1
D2
80 < HST
82
SR
SR
D1
78 < HST
80
Norm
Norm
SR
HST
78
Normal
11.7.6
Outdoor Coil Deicing Protection
11.7.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT
OAT – 8 AND TLD
<
> DI
Case 2: OCT
OAT – 12 AND TLD
30 minutes.
<
>
Case 3: OCT is Invalid AND TLD
DI
>
Case 4: Unit is ust switched to STBY AND OCT
8
-
T
A
O
<
j
Case 5: NLOAD
0 AND OCT
OAT -8
=
<
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and
is 40 minutes in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of
deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be
increased. If deicing time is longer then former deicing time, the deicing interval time will be
decreased.
(NA for GC 9 and GC 12 DCI)
Содержание PNXA 12 DCI
Страница 16: ...4 3 OUTLINE DIMENSIONS SM PNXADCI 1 A 1 GB 4 5 Outdoor Unit YBD 024...
Страница 99: ...EXPLODED VIEW SPARE PART LIST 14 6 SM PNXADCI 1 A 1 GB 14 6 Exploded view of outdoor Unit GC 9 12 DCI...
Страница 101: ...EXPLODED VIEW SPARE PART LIST 14 8 SM PNXADCI 1 A 1 GB 14 8 Exploded view of outdoor Unit YBD018...
Страница 103: ...EXPLODED VIEW SPARE PART LIST 14 10 SM PNXADCI 1 A 1 GB 14 10 Exploded view of outdoor Unit YBD022...
Страница 105: ...EXPLODED VIEW SPARE PART LIST 14 12 SM PNXADCI 1 A 1 GB 14 12 Exploded view of outdoor Unit YBD024...
Страница 108: ...APPENDIX A SM PNXADCI 1 A 1 GB 16 1 APPENDIX A INSTALLATION AND OPERATION MANUALS...