CONTROL SYSTEM
12-8
SM PNXADCI 1-A.1 GB
HST
n
is the current reading of HST and HST
n-1
is the last reading of HST.
HST
n
-HST
n-1
HST
n
<-1
-1
0
1
>1
HST
n
>
HSTOH5
SC
SC
SC
SC
SC
HSTOH4
≤ HST
n
<
HSTOH5
D1
D1
D2
D2
D2
HSTOH3
≤ HST
n
<
HSTOH4
SR
SR
D1
D2
D2
HSTOH2
≤ HST
n
<
HSTOH3
SR
SR
SR
D1
D1
HSTOH1
≤ HST
n
<
HSTOH2
Norm
Norm
Norm
SR
SR
HST
n
<
HSTOH1
Norm
(*) Normal (Norm)
– No protection status is ON.
Stop-Rise (SR)
– System is in protection.
HzDown1 (D1)
- System is in protection.
HzDown2 (D2)
- System is in protection.
12.7.7
System Over Power Protection
Power
n
-Power
n-1
Power
n
<-50
[-50,-1]
0
[1,50]
>50
Power
n
> OVRPWR5
SC
SC
SC
SC
SC
OVRPWR4
≤ Power
n
<
OVRPWR5
D1
D1
D2
D2
D2
OVRPWR3
≤ Power
n
<
OVRPWR4
SR
SR
D1
D2
D2
OVRPWR2
≤ Power
n
<
OVRPWR3
SR
SR
SR
D1
D1
OVRPWR1
≤ Power
n
<
OVRPWR2
Norm
Norm
Norm
SR
SR
Power
n
< OVRPWR1
Norm
12.7.8
Outdoor Coil Deicing Protection
In the deicing protection, IFAN is forced OFF.
12.7.8.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
•
Case 1: OCT<–DST AND TLD > DI
•
Case 2: OCT<-4 AND TLD>
100
minutes
•
Case 3: OCT is Invalid AND TLD > DI
•
Case 4: Unit is just switched to STBY AND OCT<-DST
•
Case 5: compressor is stopped during heating operation, OCT<-DST AND TLD>DI,
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
DT- Deicing Time
Содержание PNXA 12 DCI
Страница 16: ...4 3 OUTLINE DIMENSIONS SM PNXADCI 1 A 1 GB 4 5 Outdoor Unit YBD 024...
Страница 99: ...EXPLODED VIEW SPARE PART LIST 14 6 SM PNXADCI 1 A 1 GB 14 6 Exploded view of outdoor Unit GC 9 12 DCI...
Страница 101: ...EXPLODED VIEW SPARE PART LIST 14 8 SM PNXADCI 1 A 1 GB 14 8 Exploded view of outdoor Unit YBD018...
Страница 103: ...EXPLODED VIEW SPARE PART LIST 14 10 SM PNXADCI 1 A 1 GB 14 10 Exploded view of outdoor Unit YBD022...
Страница 105: ...EXPLODED VIEW SPARE PART LIST 14 12 SM PNXADCI 1 A 1 GB 14 12 Exploded view of outdoor Unit YBD024...
Страница 108: ...APPENDIX A SM PNXADCI 1 A 1 GB 16 1 APPENDIX A INSTALLATION AND OPERATION MANUALS...