11-11
CONTROL SYSTEM
SM PNXDCI 1-A.1 GB
11.13 Test
Mode
11.13.1
Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
Mode = Cool, Set point =16, Room temperature = 27±1, Outdoor temperature = 35±1
Or
Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1
Manually when entering diagnostics with the following settings:
Mode = Cool, Set point = 1 6
Mode = Heat, Set point = 30
11.13.2
Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed Setting
Unit Setting
Low
Minimum Capacity Setting
High
Nominal Capacity Setting
Auto
Maximum Capacity Setting
11.14 SW
Parameters
11.14.1
Indoor Units SW Parameters
General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode (ICT):
ICTST Speed
ICT to stop indoor fan
25
ICTVLSpeed
ICT to go down to very low speed
28
ICTLSpeed
ICT to start in very low speed
30
ICTHSpeed
ICT to start in increase speed from very low
32
ICTTSpeed
ICT to enable Turbo fan speed
40
Model Depended Parameters:
Parameter name
Wall Mounted Models
PNX009
PNX012
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C
40
40
MaxNLOADIF2C
53
53
MaxNLOADIF3C
120
120
MaxNLOADIF4C
127
127
MaxNLOADIF5C
127
127
Indoor Fan speeds
IFVLOWC
700
700
IFLOWC
800
850
IFMEDC
900
950
IFHIGHC
1050
1100
IFTURBOC
1150
1200
IFVLOWH
700
700
IFLOWH
800
850
IFMEDH
950
1000
IFHIGHH
1100
1150
IFTURBOH
1200
1300
Nominal Compressor Frequency
NomLoadC
40
62
NomLoadH
55
67