11-6
CONTROL SYSTEM
SM PNXDCI 1-A.1 GB
11.7.4
Compressor over Current Protection
11.7.5
Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST
HST Trend
Decreasing
No Change
Increasing
HST > 90
SC
SC
SC
85 < HST
≤
90
D1
D2
D2
82 < HST
≤
85
SR
D1
D2
80 < HST
≤
82
SR
SR
D1
78 < HST
≤
80
Norm
Norm
SR
HST
≤
78
Normal
11.7.6
Outdoor Coil Deicing Protection
11.7.6.1
Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
•
Case 1: OCT < -
DST
– AND TLD > DI
•
Case 2: OCT < OAT – 12 AND TLD > 30 minutes.
•
Case 3: OCT < - AND TLD > 75 minutes
•
OCT is Invalid AND OCT < 0
•
Compressor ON Time > 15 minutes
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
DST – Deicing static threshold (Temperature)
Where DST is defined as:
When OAT > 0 or OAT is invalid, then DST = 8
When OAT
≤
0 then DST = round down (- 0.7*OAT)+8
Normal
Stop-Rise
HzDown1
HzDown2
Stop-Compresor
CCROC1
CCROC2
CCROC3
CCROC4
CCR