background image

12-6

TROUBLESHOOTING 

SM PNXDCI 1-A.1 GB 

No

Fault

Probable Cause

Corrective Action

4

DC under/over Voltage

Electronics HW prob-
lem

Check outdoor unit pow-
er supply voltage 

5

AC under Voltage

Check outdoor unit pow-
er supply voltage

6

Indoor / Outdoor unit 
Communication mis-
match

Indoor and Outdoor 
controllers are with 
different versions

Replace Indoor controller

7

No Communication

Communication or 
grounding wiring is not 
good.

Check Indoor to Outdoor 
wiring and grounding

8

Compressor Lock

Switch unit to STBY and 
restart

9

Bad Communication

Communication quality is 
low reliability

Check Indoor to Outdoor 
wiring and grounding

12.4 

Judgment by MegaTool

MegaTool is a special tool to monitor the system states. 
Using MegaTool requires:  

A computer with RS232C port.

• 

A connection wire for MegaTool.

• 

A special MegaTool software.

• 

Use MegaTool according to following procedure:

• 

Setup MegaTool software: copy the software to the computer.

• 

Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit controller by the 

• 

connection wire. 
Run the software and choose the COM port, you can monitor the A/C system state  

• 

 In monitor tab    

• 

12.5 

Simple procedures for checking the Main Parts

12.5.1 

Checking Mains Voltage. 

Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, 
abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and look 
for broken or loosed cable lugs or wiring mistake(s).

12.5.2 

Checking Power Input.

If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. 
If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power 
up again.
Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit. 

12.5.3 

Checking the Outdoor Fan Motor.

Enter Test Mode (where the OFAN speed is high)
Check the voltage between lead wires according to the normal value as following:
Between red wire and black wire: /- 20V
Between orange wire and black wire: 15VDC +/- 1V
Between yellow wire and black wire: 2-6VDC

Содержание PNX DCI Nordic

Страница 1: ...PNX DCI Nordic Indoor Units Outdoor Units PNX009 DCI GC 9 DCI Nordic PNX012 DCI GC 12 DCI Nordic SEPTEMBER 2009 REFRIGERANT R410A HEAT PUMP SM PNXDCI 1 A 1 GB...

Страница 2: ...or original and changed pages are Original 0 September 2009 Total number of pages in this publication is 50 consisting of the following Page No Revision No Page No Revision No Page No Revision No Titl...

Страница 3: ...ONS 3 1 4 OUTLINE DIMENSIONS 4 1 5 PERFORMANCE DATA PRESSURE CURVES 5 1 6 SOUND LEVEL CHARACTERISTICS 6 1 7 ELECTRICAL DATA 7 1 8 WIRING DIAGRAMS 8 1 9 REFRIGERATION DIAGRAMS 9 1 10 TUBING CONNECTIONS...

Страница 4: ...er shedding functions configurable Base heater connection Cooling operation at outdoor temperature down to 10 C Heating operation at outdoor temperature down to 15 C Supports Indoor Air Quality featur...

Страница 5: ...presents several types of air filters Easily accessible and re usable pre filters mesh Pre charged electrostatic filter disposable Active carbon filter disposable ESF Active Electro Static re usable...

Страница 6: ...ble speed DC Inverter M2L cable Port No 1 8 Tubing Connections Flare type interconnecting tubing to be produced on site For further details please refer to the Installation Manual 1 9 Accessories Item...

Страница 7: ...202 285 Weight kg 11 Packing dimensions W D H mm 885 285 360 Unit stacking units 7 OUTDOOR UNIT Refrigerant control Electronic Expansion Valve Compressor type Scroll DC Inverter Compressor Model Matsu...

Страница 8: ...acking dimensions W D H mm 885 285 360 Unit stacking units 7 OUTDOOR UNIT Refrigerant control Electronical Expansion Valve Compressor type Scroll DC Inverter Compressor Model Matsushita 5CS102XDA04 St...

Страница 9: ...Cooling Indoor 27o C DB 19o C WB Outdoor 35 o C DB Heating Indoor 20o C DB Outdoor 7o C DB 6o C WB 3 1 Operating Limits 3 1 1 R410A Indoor Outdoor Cooling Upper limit 32o C DB 23o C WB 46o C DB Lower...

Страница 10: ...AIR INTAKE AIR INTAKE AIR OUTLET 210 285 811 CEELING 8 0 83 0 167 5 100 0 MIN 83 0 8 0 18 5 30 0 MOUTING PLATE OUTLINE MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL 167 5 810 0...

Страница 11: ...2 77 2 92 SC 1 65 1 67 1 70 1072 1 75 PI 0 53 0 54 0 55 0 57 0 58 35 TC 2 21 2 36 2 50 2 65 2 79 SC 1 58 1 60 1 63 1 66 1 68 PI 0 60 0 61 0 62 0 63 0 64 40 TC 2 08 2 23 2 37 2 52 2 66 SC 1 51 1 54 1...

Страница 12: ...4 0 78 0 82 2 1 TC 2 72 2 50 2 28 PI 0 76 0 80 0 84 7 6 TC 3 62 3 40 3 18 PI 0 79 0 83 0 87 10 9 TC 3 81 3 59 3 36 PI 0 80 0 86 0 89 15 12 TC 4 00 3 78 3 55 PI 0 82 0 86 0 90 15 24 TC 85 105 of nomina...

Страница 13: ...to Tubing Length 5 2 1 Cooling 0 91 0 92 0 93 0 94 0 95 0 96 0 97 0 98 0 99 1 00 1 01 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Tubing Length m Capacity Ratio 5 2 2 Heating 0 90 0 92 0 94 0 96 0...

Страница 14: ...8 SC 2 40 2 44 2 48 2 51 2 55 PI 0 90 0 91 0 93 0 95 0 97 35 TC 3 09 3 30 3 50 3 70 3 91 SC 2 31 2 34 2 38 2 42 2 45 PI 1 00 1 02 1 04 1 06 1 08 40 TC 2 92 3 12 3 32 3 53 3 73 SC 2 21 2 25 2 28 2 32 2...

Страница 15: ...2 1 TC 3 36 3 09 2 81 PI 1 04 1 10 1 16 7 6 TC 4 48 4 20 3 92 PI 1 08 1 14 1 20 10 9 TC 4 71 4 43 4 16 PI 1 10 1 16 1 22 15 12 TC 4 94 4 66 4 39 PI 1 12 1 18 1 24 15 24 TC 85 105 of nominal Protection...

Страница 16: ...to TUbing Length 5 4 1 Cooling 0 91 0 92 0 93 0 94 0 95 0 96 0 97 0 98 0 99 1 00 1 01 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Tubing Length m Capacity Ratio 5 4 2 Heating 0 90 0 92 0 94 0 96 0...

Страница 17: ...5 7 PERFORMANCE DATA PRESSURE CURVES SM PNXDCI 1 A 1 GB 5 5 Pressure Curves 5 5 1 Model PNX009 GC 9 DCI Nordic Cooling Test Mode...

Страница 18: ...5 8 PERFORMANCE DATA PRESSURE CURVES SM PNXDCI 1 A 1 GB 5 5 2 Cooling Test Mode...

Страница 19: ...5 9 PERFORMANCE DATA PRESSURE CURVES SM PNXDCI 1 A 1 GB 5 6 Pressure Curves 5 6 1 Model PNX012 GC 12 DCI Nordic Cooling Test Mode...

Страница 20: ...5 10 PERFORMANCE DATA PRESSURE CURVES SM PNXDCI 1 A 1 GB 5 6 2 Heating Test Mode...

Страница 21: ...E HI ME LO 1m 0 8m Mic Unit Wall Hz AND CE TER FREQUENC ES APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 70NC 60NC 50NC 40NC 30NC 20NC MICRO AR0 02 dB re OCT VE BAN S UN PRES URE L VEL Hz AND...

Страница 22: ...EVEL CHARACTERISTICS SM PNXDCI 1 A 1 GB 6 3 Outdoor units 6 4 Sound Pressure Level Spectrum Measured as Figure 2 GC 9 DCI Cooling GC 9 DCI Heating GC 12 DCI Cooling GC 12 DCI Heating 1m Mic Unit Groun...

Страница 23: ...35A Starting Current b 10A Circuit Breaker 16A Power Supply wiring no x cross section 3 X 1 5 mm Interconnecting cable no x cross section 4 X 1 5 mm a Inrush current is the current when power is up ch...

Страница 24: ...8 1 WIRING DIAGRAMS SM PNXDCI 1 A 1 GB 8 WIRING DIAGRAMS 8 1 Indoor Outdoor Units PNX009 PNX012 GC 9 DCI Nordic GC 12 DCI Nordic...

Страница 25: ...DIAGRAMS SM PNXDCI 1 A 1 GB 9 REFRIGERATION DIAGRAMS 9 1 Heat Pump Models 9 1 1 PNX009 GC 9 DCI Nordic PNX012 GC 12 DCI Nordic Cooling Mode 9 1 2 PNX009 GC 9 DCI Nordic PNX012 GC 12 DCI Nordic Heatin...

Страница 26: ...13 1 Valve Protection Cap end 2 Refrigerant Valve Port use Allen wrench to open close 3 Valve Protection Cap 4 Refrigerant Valve 5 Service Port Cap 6 Flare Nut 7 Unit Back Side 8 Copper Tube When the...

Страница 27: ...sents the heat or cool load felt by the indoor unit 11 1 2 Compressor Frequency Control 11 1 2 1 NLOAD setting The NLOAD setting is done by the indoor unit controller based on a PI control scheme The...

Страница 28: ...temperature 22 for cooling or 25 for heating 11 1 8 Heating Element Control Heating element can be started if LOAD 0 8 MaximumNLOAD AND Indoor Coil temperature 45 The heating element will be stopped w...

Страница 29: ...the EEVOL Parameters Table EEV correction setting EEVcvpart EEVcv is a collection EEV value it s calculated as follows EEV cv 0 during the first 1 minutes after the compressor starts After 1 minutes a...

Страница 30: ...oller Model J2 Shorted J2 Opened Wall Mounted PNX Compensation Disable Compensational Enabled 11 4 2 Indoor Fan Control in Heat Mode Indoor fan speed depends on the indoor coil temperature 11 5 Auto C...

Страница 31: ...Trend Fast Decreasing Decreasing No Change Increasing Fast Increasing ICT 55 SC SC SC SC SC 53 ICT 55 D1 D1 D2 D2 D2 49 ICT 53 SR SR D1 D2 D2 47 ICT 49 SR SR SR D1 D2 45 ICT 47 Norm Norm SR SR D1 43 I...

Страница 32: ...operation will start when either one of the following conditions exist Case 1 OCT DST AND TLD DI Case 2 OCT OAT 12 AND TLD 30 minutes Case 3 OCT AND TLD 75 minutes OCT is Invalid AND OCT 0 Compressor...

Страница 33: ...Water Over Flow Protection Each of the pins P1 P2 P3 can have two options 1 When it is shorted with P4 0 When it is not shorted to P4 11 8 1 3 Levels Logic used in floor ceiling models P2 P3 Level 0 0...

Страница 34: ...orced to STBY J8 Open Power Shedding Function No Limit Limit NLOAD 11 10 Operating the Unit from the Mode Button Forced operation allows to start stop and operate in Cooling or Heating in pre set temp...

Страница 35: ...operation mode is selected in this order SB Cool Mode Heat Mode SB In long pressing system enters diagnostic mode RESET FILTER SWITCH For short pressing When Filter LED is on turn off the FILTER INDIC...

Страница 36: ...table and factory default cannot be changed by service Model selection Jumper J7 J8 Model J7 J8 A B C D 0 0 0 1 1 0 1 1 J9 Presence Detector Power Shedding OPERATION J9 Presence Detector 0 Power Shed...

Страница 37: ...Setting 11 14 SW Parameters 11 14 1 Indoor Units SW Parameters General Parameters for All Models Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode ICT ICT...

Страница 38: ...FreqH 30 30 MaxFreqH 78 88 Step1Freq 35 35 Step2Freq 50 55 Step3Freq 90 90 Frequency limits as a function of outdoor air temperature MaxFreqAsOATC 40 50 MaxFreqAsOAT1H 65 75 MaxFreqAsOAT2H 50 60 Compr...

Страница 39: ...er 3 Unit responds to remote control message but Operate indicator Green LED does not light up Problem with display PCB Replace display PCB If still not OK replace controller 4 Indoor fan does not sta...

Страница 40: ...is generating noise and no suction occurs Phase order to compressor is wrong Check compressor phase order 14 Water leakage from indoor unit Indoor unit drainage tube is blocked Check and open drainag...

Страница 41: ...em has recovered from that fault The last fault will be deleted from the EEPROM after the system has exit diagnostics mode In diagnostics mode system fault status will be indicated by blinking of Heat...

Страница 42: ...and grounding 4 No Encoder Indoor electronics or motor Check motor wiring if ok replace motor if still not ok replace Indoor controller 5 Outdoor Unit Fault Outdoor controller problem Switch to Outdo...

Страница 43: ...0 0 0 17 No Communication 1 0 0 0 1 18 Reserved 1 0 0 1 0 20 Heat sink Over Heating 1 0 1 0 0 21 Deicing 1 0 1 0 1 22 Compressor Over Heating 1 0 1 1 0 23 Compressor Over Current 1 0 1 1 1 24 No OFAN...

Страница 44: ...232C port in computer with MegaTool port in Indoor Outdoor unit controller by the connection wire Run the software and choose the COM port you can monitor the A C system state In monitor tab 12 5 Simp...

Страница 45: ...ole controller including the wires that are connected to the Outdoor unit controller may have the potential hazard voltage when power is on Touching the Outdoor unit controller may cause an electrical...

Страница 46: ...13 1 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 13 EXPLODED VIEWS AND SPARE PARTS LISTS 13 1 Indoor Unit PNX009 PNX012 DCI...

Страница 47: ...1 17 4518650 Motor Cover 1 18 452969400 Step Motor A 1 452969500 Step Motor B 1 19 4521158R Power cord cable Euro 1 4520061R Power cord cable Israel 1 4520278R Power cord cable Without plug 1 20 45191...

Страница 48: ...13 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 13 4 Outdoor Unit GC 9 DCI Nordic GC 12 DCI Nordic...

Страница 49: ...94R Controller 1 24 467400027 Outside air thermistor OAT 1 24 4526775 Compressor top thermistor CTT 1 24 467400030 Outside coil thermistor OCT 1 24 467400031 Outside middle coil thermistor OIVIT 1 25...

Страница 50: ...14 1 APPENDIX A SM PNXDCI 1 A 1 GB APPENDIX A INSTALLATION AND OPERATION MANUALS INSTALLATION MANUAL PNX009 PNX012 DCI OPERATING MANUAL PNX009 PNX012 DCI...

Отзывы: