11-1
CONTROL SYSTEM
SM PNXDCI 1-A.1 GB
11. CONTROL
SYSTEM
11.1
General Functions and Operating Rules
The DCI software is fully parametric.
All the model dependent parameters are shown in Italic style [
parameter].
The parameters values are given in the last section of this control logic chapter of the service
manual.
11.1.1
System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the System ‘Master’, requesting
the outdoor unit for cooling/heating capacity supply. The outdoor unit is the system ‘Slave’ and it must supply the required
capacity nless it enters into a protection mode avoiding it from supplying the requested capacity.
The capacity request is transferred via indoor to outdoor communication, and is represented by a parameter called
‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it represents the heat or cool load felt by the
indoor unit.
11.1.2
Compressor Frequency Control
11.1.2.1
NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme. The actual NLOAD to be sent to
the outdoor unit controller is based on the preliminary LOAD calculation, the indoor fan speed, and the power shedding
function.
NLOAD limits as a function of indoor fan speed:
Indoor Fan Speed
Maximum NLOAD Cooling
Maximum NLOAD Heating
Low
Max NLOADIF1C
127
Medium
Max NLOADIF2C
127
High
Max NLOADIF3C
127
Turbo
Max NLOADIF4C
127
Auto
Max NLOADIF5C
127
NLOAD limits as a function of power shedding:
Mode
Power Shedding OFF
Power Shedding ON
Cool
No limit
Nominal Cooling
Heat
No limit
Nominal Heating
NLOAD limits as a function of indoor fan speed:
NLOAD
Target Frequency [Hz]
0
0
0<NLOAD
≤
MinFreq
MiniFreq
>MinFreq
MaxFreq
─
MinFreq
127
─
MinFreq
Target frequency limits as a function of outdoor air temperature (OAT):
OAT Range
Cool mode limits
Heat mode limits
O AT < 6
MaxFreqAsOATC
No limit
6 < O AT < 1 5
MaxFreqAsOATIH
15 < OAT < 24
MaxFreqAsOAT2H
24 < OAT
No limit