![Airwell DLS 30 DCI Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/airwell/dls-30-dci/dls-30-dci_service-manual_2880105091.webp)
12-16
CONTROL SYSTEM
SM DLSDCI 3-A.1 GB
12.4.6
Dry Mode
12.4.6.1 DRY - General
a. Mode Definition
Mode: DRY
Temp: Selected desired temperature
Fan:
LOW (automatically selected by software)
Timer: Any
I-FEEL: ON or OFF
12.4.6.2 Control function
a. COMP Operation
In general – the operation is set by the NLOAD calculation in indoor unit side.
Other rules are according to section 12.5.1
.
b. OFAN Operation
In normal operation OFAN operates together with the COMP.
Other rules are according to section 12.5.3
.
c. IFAN Operation
LOW only.
d. RV
RV is in OFF state during DRY mode.
e. HEATERS
HEATERS are in OFF state during DRY mode.
f. Pump
Pump operates in cool/dry mode.
12.4.6.3 Sequence Diagrams
Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with
LOW speed IFAN.
TROUBLESHOOTING
Service Manual
Multi Cinco 100 DCI
12-20
Revision 0
min{
MaxNLO ExtraNLOADDry
,127}
RAT-SPT
IFAN Low
0
IFANOnTimeDry
MaxNLOADIF1C
NLOAD
ICTLowLimitDry
ICTHighLimitDry
Note 1
IFANOffTimeDry
Note 1
NLOAD
0
Note 1
Min(ICT,ICTE)
1
12.4.7
Sleep Mode
12.4.7.1
Sleep Mode - General
a. Mode Definition
Mode: Any
Temp: Selected desired temperature
IFan: Any
Timer: See below
I-FEEL: ON or OFF
12.4.7.2
Control function
o
The Sleep mode is activated by using the SLEEP button on the R/C. In Sleep
Mode, the unit will automatically adjust the SPT to turn up/down the room
temperature (RT) gradually to provide maximum comfort for the sleeping user.
o
Sleep is treated as TIMER function. Therefore, the TIMER LED is activated similar
to TIMER function.