![Airwell DLS 30 DCI Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/airwell/dls-30-dci/dls-30-dci_service-manual_2880105011.webp)
2-4
PRODUCT DATA SHEET
SM DLSDCI 3-A.1 GB
2.4 DLS 36 DCI 1PH
Model Indoor Unit
DLS 36 DCI R410A AW
Model Outdoor Unit
AWAU-YBD036-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Warmer
Pdesign
kW
8.5
10.2
10.2
SEER / SCOP
W/W
4.2
3.5
4.1
Energy efficiency class
C
A
A+
Annual energy consumption
kWh
1,658
6,014
2,985
Tbiv
o
C
N/A
-3
6
Tol
o
C
N/A
-15
-10
Capacity Range
(1)
(min÷max)
kW
2.8÷11.2
2.7÷12.5
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating
A
25
INDOOR
Fan type & quantity
Centrifugal x 1
Fan speeds
H/M/L
RPM
870 / 650 / 560
Air flow
(2)
H/M/L
m
3
/hr
1750/1500/1210
External static pressure
Min-Max
Pa
37-100
Sound power level
(3)
H/M/L
dB(A)
65 / 60 / 55
Sound pressure level
(4)
H/M/L
dB(A)
52 / 49 / 47
Moisture removal
l/hr
3.3
Condensate drain tube I.D
mm
19
Dimensions
WxHxD
mm
854x297x816
Weight
kg
33
Package dimensions
WxHxD
mm
1005x345x915
Packaged weight
kg
35.5
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Twin Rotary DC Inverter
Fan type & quantity
Axial x 2
Fan speeds
RPM
950-200(continuous)
Air flow
Max.
m3/hr
4,150
Sound power level
Nom.
dB(A)
69
Sound pressure level
Nom.
dB(A)
58
Dimensions
WxHxD
mm
900x970x340
Weight
kg
85
Package dimensions
WxHxD
mm
985x1020x435
Packaged weight
kg
87.8
Units per pallet
Units
6 units per pallet
Stacking height
units
2 levels
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(7.5m)
2.50
Additional charge (tubing length 30÷70m)
gr/m
30
Connections
between units
Liquid line
In.(mm)
3/8”(9.53)
Suction line
In.(mm)
5/8”(15.875)
Max.tubing length
m.
70
Max.height difference
m.
30
Operation control type
Remote control
Heating elements
kW
BH 70W - optional
Others
(1) Rating conditions in accordance with EN14825 and EN14511 (for ducted units).
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1.0 meter distance from unit.