5-14
PERFORMANCE DATA & PRESSURE CURVES
SM DLSDCI 3-A.1 GB
ID COIL ENTERING AIR DB
TEMPERATURE [°C]
OD COIL
ENTERING AIR
DB/WB
TEMPERATURE
[°C]
DATA
15 20 25
-15/-16
TC 6.49 6.04 5.58
PI 1.62
1.79
1.95
-10/-12
TC 7.23 6.77 6.32
PI 1.95 2.12 2.28
-7/-8
TC 7.78 7.32 6.87
PI 2.20 2.37 2.53
-1/-2
TC 8.05 7.60 7.15
PI 2.33 2.49 2.66
2/1
TC 8.24 7.78 7.33
PI 2.41 2.58 2.74
7/6
TC 10.65
10.20
9.75
PI 2.54
2.70
2.86
10/9
TC 11.24 10.79 10.33
PI 2.69 2.85 3.02
15/12
TC 11.83 11.38 10.92
PI 2.84
3.00
3.17
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
5.4.2
Heating Capacity
LEGEND
TC - Total Cooling Capacity, KW
SC - Sensible Capacity, KW
PI - Power Input, KW
WB - Wet Bulb Temp. (
⁰
C)
DB - Dry Bulb Temp. (
⁰
C)
ID - Indoor
OD - Outdoor