Safety Precautions

Precautions for Handling Units for Use with R410A

Do not use the existing refrigerant piping

The old refrigerant and refrigerator oil in the existing piping

contain a large amount of chlorine, which will cause the

refrigerator oil in the new unit to deteriorate.

R410A is a high-pressure refrigerant, and the use of the

existing piping may result in bursting.

Keep the inner and outer surfaces of the pipes clean and

free of contaminants such as sulfur, oxides, dust/dirt shaving

particles,oils,and moisture.

Contaminants inside the refrigerant piping will cause the

refrigerant oil to deteriorate.

Use a vacuum pump with a reverse-flow check valve.

If other types of valves are used, the vacuum pump oil will

flow back into the refrigerant cycle and cause the refrigerator

oil to deteriorate.

Do not use the following tools that have been used with the

conventional refrigerants. Prepare tools that are for exclusive

use with R410A.

(Gauge manifold, charging hose, gas leak detector,

reverse-flow check valve, refrigerant charge base,vacuum

gauge, and refrigerant recovery equipment.)

If refrigerant and/or refrigerant oil left on these tools are

mixed in with R410, or if water is mixed with R410A, it will

cause the refrigerant to deteriorate.

Since R410A does not contain chlorine, gas-leak detectors

for conventional refrigerators will not work.

Store the piping to be used during installation indoors, and

keep both ends of the piping sealed until immediately before

brazing.(keep elbows and other joints wrapped in plastic.)

If dust, dirt, or water enters the refrigerant cycle, it may

cause the oil in the unit to deteriorate or may cause the

compressor to malfunction.

A large amount of mineral oil will cause the refrigerating

machine oil to deteriorate.

Use a small amount of ester oil, ether oil, or alkylbenzene

to coat flares and flange connections.

Use liquid refrigerant to charge the system.

Charge the unit with gas refrigerant will cause the  refrigerant

in the cylinder to change its composition and will lead to

a drop in performance

Do not use a charging cylinder.

The use of charging cylinder will change the composition

of the refrigerant and lead to power loss.

Exercise special care when handling the tools.

An introduction of foreign objects such as dust, dirt or

water into the refrigerant cycle will cause the refrigerating

machine oil to deteriorate.

Only use R410A refrigerant.

The use of refrigerants containing chlorine(i.e. R22) will

cause the refrigerant to deteriorate.

Before Installing the Unit

Do not install the unit in a place where there is a possibility

of flammable gas leak.

Leaked gas accumulated around the unit may start a fire.

Do not use the unit to preserve food, animals, plants, artifacts,

or for other special purposes.

The unit is not designed to provide adepuate conditions

to preserve the quality of these items.

Do not use the unit in an unusual environment

The use of the unit in the presence of a large amount of

oil, steam, acid, alkaline solvents or special types of sprays

may lead to a remarkable drop in performance and/or

malfunction and presents a risk of electric shock, smoke,

or fire.

The presence of organic solvents, corroded gas (such as

ammonia,sulfur compounds,and acid may cause gas or

water leak.)

When installing the unit in a hospital, take necessary measures

against noise.

High-frequency medical equipment may interfere with the

normal operation of the air conditioning unit or the air

conditioning unit may interfere with the normal operation

of the medical equipment

When humidity level exceeds 80% or when the drainage

system is clogged, indoor units may drip water.

Installation of a centralized drainage system for the outdoor

unit may also need to be considered to prevent water drips

from the outdoor units.

Do not place the unit on or over things that may not get wet.

Caution

Caution

Caution

Содержание AWAU-YUDA060-H13

Страница 1: ...OUTDOOR UNIT INSTALLATION MANUAL EN Please read this manual carefully before using this air conditioner Please keep this manual safely for future use R410A AWAU YUDA060 H13...

Страница 2: ......

Страница 3: ......

Страница 4: ...be checked for any damages If the damaged base is not repaired the unit may fall down and cause accidents When need maintenance and repairment call dealer to handle it Incorrect maintenance and repai...

Страница 5: ...to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of a refrigerant gas leak provide adequate ventilation to the room If leaked refrigerant gas is exposed to a heat...

Страница 6: ...at flares and flange connections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to...

Страница 7: ...ling draining pipes follow the instructions in the manual and make sure that they properly drain water so as to avoid dew condensation If not installed properly they may cause water leaks and damage t...

Страница 8: ...Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the...

Страница 9: ...ess If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe protrusi...

Страница 10: ...il from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degre...

Страница 11: ...10 Name of Parts Air inlet Air outlet Compressor Inside of unit YUDA060 YUDA060 will be used as brief model name in this manual AWAU H13...

Страница 12: ...acles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or more of ove...

Страница 13: ...Installation Procedure 3 Installation dimension Unit mm 12 Installation of Outdoor Unit YUDA060 580 25 1250 948 380 340...

Страница 14: ...l not to let foreign matters such as sands enter the pipe 4 Piping connection method Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Verti...

Страница 15: ...M g additional refrigerant per meter That is Refrigerant charging amount L 5m x 45 g m Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature will cause a var...

Страница 16: ...the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerant...

Страница 17: ...broken please change it with the type of T3 15A 250VAC But for YUDA060 the type is T6 3A 250VAC The wiring method should be in line with the local wiring standard The power cable and connecting cable...

Страница 18: ...RIC POWER IS SUPPLIED BE SURE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before...

Страница 19: ...Troubleshooting 18...

Страница 20: ......

Отзывы: