Installation Procedure

14

The air tightness test adopts nitrogen tank to give pressure according to the pipe connection mode as the following figure

shown.

The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the circulation system of outdoor

unit, tighten the valve rod before giving pressure (both gas and liquid valve rods).

In 1) to 3) steps, if the pressure drops, check the leakage in each joint by listening, touching and using soap water etc.

to identify the leaking point. After confirming the leaking point, welding it again or tighten the nut tightly again.

Checking the leaking point

1) Pressurize for over 3 minutes at 0.3MPa (3.0 kg/cm

2

g).

2) Pressurize for over 3 minutes at 1.5MPa (15 kg/cm

2

g). A large

    leakage will be found.

3) Pressurize for about 24 hours at 3.0MPa (30 kg/cm

2

g). A small

    leakage will be found.

Installation Procedure

When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary to charge additional

refrigerant.

If the connecting pipe (L) exceeds 5m, it shall charge M(g) additional refrigerant per meter.

That is: Refrigerant charging amount = (L-5m) x 45 (g/m)

Air Tightness Test

When pressurizing for 24 hours, a variation of 1 C in the ambient temperature will cause a variation of 0.01MPa(0.1kg/cm

2

g)

in pressure. It shall be corrected during test.

Check if the pressure drops

If the pressure does not drop, then pass.

If the pressure drops, then please check the leaking point.

Additional Refrigerant Charge

Outdoor

Completely tightened

Completely tightened

Flare part

Outdoor units

Manhole

Discharging valve

stop valve totally closed

(Gas side)

Low pressure piezometer

High pressure piezometer

Meter separator

Dropping valve

stop valve totally closed

(Liquid side)

Nitrogen tank

VL VH

Indoor units

Indoor

Flare part

After finishing connection of refrigerant pipe, it shall perform air tightness test.

Only in COOLING operation can charge the additional refrigerant.

When charging, the refrigerant shall be charged from the charging nozzle of low pressure valve.

Be carefull when charging refrigerant, do not let the air mix into the system, and must charge the additional refrigerant

in liquid state.

Cylinder pressure gauge

Cylinder of nitrogern

Line pressure gauge

Tubing bring brazed

Sweat joint

Large slip-on connector

Service hose

Содержание AWAU-YUDA060-H13

Страница 1: ...OUTDOOR UNIT INSTALLATION MANUAL EN Please read this manual carefully before using this air conditioner Please keep this manual safely for future use R410A AWAU YUDA060 H13...

Страница 2: ......

Страница 3: ......

Страница 4: ...be checked for any damages If the damaged base is not repaired the unit may fall down and cause accidents When need maintenance and repairment call dealer to handle it Incorrect maintenance and repai...

Страница 5: ...to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of a refrigerant gas leak provide adequate ventilation to the room If leaked refrigerant gas is exposed to a heat...

Страница 6: ...at flares and flange connections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to...

Страница 7: ...ling draining pipes follow the instructions in the manual and make sure that they properly drain water so as to avoid dew condensation If not installed properly they may cause water leaks and damage t...

Страница 8: ...Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the...

Страница 9: ...ess If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe protrusi...

Страница 10: ...il from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degre...

Страница 11: ...10 Name of Parts Air inlet Air outlet Compressor Inside of unit YUDA060 YUDA060 will be used as brief model name in this manual AWAU H13...

Страница 12: ...acles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or more of ove...

Страница 13: ...Installation Procedure 3 Installation dimension Unit mm 12 Installation of Outdoor Unit YUDA060 580 25 1250 948 380 340...

Страница 14: ...l not to let foreign matters such as sands enter the pipe 4 Piping connection method Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Verti...

Страница 15: ...M g additional refrigerant per meter That is Refrigerant charging amount L 5m x 45 g m Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature will cause a var...

Страница 16: ...the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerant...

Страница 17: ...broken please change it with the type of T3 15A 250VAC But for YUDA060 the type is T6 3A 250VAC The wiring method should be in line with the local wiring standard The power cable and connecting cable...

Страница 18: ...RIC POWER IS SUPPLIED BE SURE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before...

Страница 19: ...Troubleshooting 18...

Страница 20: ......

Отзывы: