Installation Procedure

16

Electrical Wiring

Selection of size of power supply and interconnecting wires

Precautions for Electrical wiring

Electrical wiring work should be conducted only by authorized personnel.

Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated

grip on the ends of the wires.

Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage

drop.)

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC

CONNECTIONS.

GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

WARNING!

If the supply cord is damaged, it must be replaced by the manufacturer or itsservice agent or a similar qualified person.

If the fuse of control box is broken, please change it with the type of T25A/450VAC;

If the fuse of control PC board is broken, please change it with the type of T3.15A/250VAC. But for 

YUDA060

, the type

is T6.3A/250VAC.

The wiring method should be in line with the local wiring standard.

The power cable and connecting cable should be self-provided.

All the cables shall have got the European authentication certificate. During installation, when the connecting cables

break off, it must be assured that the grouding wire is the last one to be broken off.

The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should not be no

less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.

The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the

diameter of the wire should be enlarged according to the local wiring standard.

A leakage breaker must  be installed.

The specification of power cable

Item

Model

Phase

Switch breaker

(A)

Circuit  breaker

Overcurrent protector

rated capacity (A)

Power source

wire size

(minimum)

(mm

2

)

Switch

breaker(A)

Earth leakage breaker

Leak

current(mA)

YUDA060

3

30

4.0

30

20

30

For model 

YUDA060

, the power cable should be H07RN-F 5G 4.0mm

2

.

Содержание AWAU-YUDA060-H13

Страница 1: ...OUTDOOR UNIT INSTALLATION MANUAL EN Please read this manual carefully before using this air conditioner Please keep this manual safely for future use R410A AWAU YUDA060 H13...

Страница 2: ......

Страница 3: ......

Страница 4: ...be checked for any damages If the damaged base is not repaired the unit may fall down and cause accidents When need maintenance and repairment call dealer to handle it Incorrect maintenance and repai...

Страница 5: ...to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of a refrigerant gas leak provide adequate ventilation to the room If leaked refrigerant gas is exposed to a heat...

Страница 6: ...at flares and flange connections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to...

Страница 7: ...ling draining pipes follow the instructions in the manual and make sure that they properly drain water so as to avoid dew condensation If not installed properly they may cause water leaks and damage t...

Страница 8: ...Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the...

Страница 9: ...ess If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe protrusi...

Страница 10: ...il from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degre...

Страница 11: ...10 Name of Parts Air inlet Air outlet Compressor Inside of unit YUDA060 YUDA060 will be used as brief model name in this manual AWAU H13...

Страница 12: ...acles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or more of ove...

Страница 13: ...Installation Procedure 3 Installation dimension Unit mm 12 Installation of Outdoor Unit YUDA060 580 25 1250 948 380 340...

Страница 14: ...l not to let foreign matters such as sands enter the pipe 4 Piping connection method Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Verti...

Страница 15: ...M g additional refrigerant per meter That is Refrigerant charging amount L 5m x 45 g m Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature will cause a var...

Страница 16: ...the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerant...

Страница 17: ...broken please change it with the type of T3 15A 250VAC But for YUDA060 the type is T6 3A 250VAC The wiring method should be in line with the local wiring standard The power cable and connecting cable...

Страница 18: ...RIC POWER IS SUPPLIED BE SURE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before...

Страница 19: ...Troubleshooting 18...

Страница 20: ......

Отзывы: