51
9 - MAINTENANCE
A
Curved pincer
B
Spring
C
Wire
Cleaning of the electrostatic filter
MATERIALS NECESSARY FOR MAINTENANCE
1. Acid detergent CRIC10099
2. plastic or steel tank (750x750x310 mm) with settling bottom
3. Protective gloves and goggles;
4. Graduated jug;
5. Pump for manual or pneumatic spraying.
Do not use aluminum tanks or galvanized.
Foresee a stainless steel frame that keeps the filters lifted
from the tank base to have a settling bottom for the muds.
1. Position the filter to be washed on a support to facilitate
work.
2. Prepare a tank with a solution of CRIC10099 detergent
and water at 1÷20.
3. Immerse the filter in this solution
4. Ensure the solution covers the entire filter
5. Immerse it for about 5-7 minutes. A slight chemical
reaction is noticed within 2÷3 minutes with the
development of foam indicating the occurred elimination of
residues.
6. Rinse the filter with a jet of water or using a low-pressure
water jet machine.
7. Leave the electrostatic cells to dry in a hot room or directly
in the sun for a few hours.
Keep the cells lifted from the ground using two metal or
wooden laths.
8. Check the ionisation wires before remounting the filter.
The cleaner can be used to clean about 20 filters.
Can be recovered and placed in plastic containers closed; the
air oxidizes the cleaner and reduces its effectiveness
IONISATION WIRES
The impurities can determine oxidation or scaling on the
wires, which can be removed using a cloth soaked in alcohol
or an abrasive scourer with very fine grain.
Due to the high voltage powering them, the ionisation wires
are subject to wear.
To foresee a yearly replacement OF ALL WIRES avoids
unexpected breaks.
In case of break: :
1. remove all wire pieces present in the cell and remove the
springs stretching the wire;
2. hook the spring to the wire eyelet;
3. grip the ionisation wire with curved beaks pliers;
4. hook the top of the spring with the open eyelet to the wire
stretcher rod of the electrostatic cell;
5. keeping the ionisation wire stretched, with the other hand
hook it to the other wire stretching rod, always by means
of the curved beaks pliers.