6 - ELECTRIC CONNECTIONS
X1
Remote summer-winter selector switch (heat/cool)
It allows the change of the operating mode from
heating to cooling from an external control.
•
Set parameter 161
= 0 only from keypad/thermostat
= 1 control only from remote control
On - Off
Remove the jumper
12cn1 and 12a
on the
X1
terminal
block
•
Set parameter 162 :
= 0 only from keypad/thermostat
= 1 control only from remote control
Silent
It reduces the fan speed.
•
Set parameter 224
= 0 disabled
= 1 from digital input
= 2 digital / supervisor input
Ventilation (fan)
Only the fans are actives and no check on the
temperature and humidity is performed ( compressor,
humidifier and resistances are disabled).
Fire signalling (alarm AI)
REMOTE CONTROLS
HUMIDIFIER OPTION
Refer to the unit electrical diagram (the number of the diagram is shown on the serial number label).
Remove the jumper (P) on the terminal block if the control is used
The control connect