45
Par Description
Extended description
UM
default Pass.*
1
OnModeMan
Operating mode manual selection enabling
1
0
2
TempH2OHeat
Water temperature in heating
°C
30
1
3
TempH2OCool
Water temperature in cooling
°C
20
1
4
OnSetMan
Manual ambient setpoint enabling
1
0
6
DeadZone
Dead zone between winter and summer set
°C
2
1
7
Text0
Setpoint compensation: external 0 temperature
°C
15
1
8
Text1
Setpoint compensation: external 1 temperature
°C
18
1
9
Text2
Setpoint compensation: external 2 temperature
°C
21
1
10 Text3
Setpoint compensation: external 3 temperature
°C
24
1
11 Text4
Setpoint compensation: external 4 temperature
°C
30
1
12 Set0
Setpoint compensation: value 0
°C
19
1
13 Set1
Setpoint compensation: value 1
°C
21
1
14 Set2
Setpoint compensation: value 2
°C
23
1
15 Set3
Setpoint compensation: value 3
°C
25
1
16 Set4
Setpoint compensation: value 4
°C
27
1
17 ExtRecManager
Enables the recovery compressor management at supervisor charge
0
1
18 BandPR
Proportional band
°C
2
1
19 DeltaHeatAmb
Dead zone (VheatAmb)
°C
3
1
20 BandHeatRec
Proportional band (VheatExt)
°C
10
1
21 DeltaHeatRec
Dead zone (VheatExt)
°C
3
1
22 RecInteg
Water coil operating enabling only in integration
1
1
24 LimTextHeat
External temp. limit for the compressor operating in heating
°C
-
15
1
25 TextCompOn
External temperature limit below which the compressor is always on
°C
10
1
26 SetOutHeat
Outlet SetPoint in heating
°C
-
3
1
27 DeltaSetOutHeat
Setpoint variation range in Heat outlet
°C
20
1
28 BandOutHeat
Water coil modulation band in heating
°C
2
1
30 SetURHeat
UR SetPoint in heating
%
55
0
31 BandURHeat
UR humidity control band in winter ambient
%
10
1
32 SetUROut
Outlet limit humidity in heating
%
90
1
33 BandUROut
Outlet limit humidity control band
%
10
1
34 MaxOut
Humidifier control signal max. value
%
100
1
35 LimTextCool
Compressor external temperature limit in cooling
°C
40
1
36 BandCoolRec
Proportional band (VCoolExt)
°C
5
1
37 DeltaCoolRec
Dead zone (VCoolExt)
°C
3
1
38 DeltaCoolAmb
Dead zone (VCoolAmb)
°C
5
1
40 SetOutCool
Outlet SetPoint in cooling
°C
-
2
1
41 DeltaSetOutCool
Setpoint variation range in Cool outlet
°C
5
1
42 BandOutCool
Water coil modulation band in cooling
°C
2
1
44 LimOutDC
Outlet temperature limit during the dehumidification
°C
23
1
45 BandLimOutDC
Outlet temperature limit control band during the dehumidification
°C
2
1
46 TimeStart
Fan starting time
sec
60
1
47 TimeStop
Fan stopping time
sec
60
1
48 TextStopFanHeat
Ventilation stop external temp. in Heat
°C
-
15
1
49 TambStopFanHeat
Ventilation stop ambient temp. in Heat
°C
10
1
50 TextStopFanCool
Ventilation stop external temp. in Cool
°C
38
1
51 TambStopFanCool
Ventilation stop ambient temp. in Cool
°C
30
1
54 TimeCycle
Time between ventilation stop and start
sec
1800
1
88 TimeThrow
Permanence max. time of the outlet temperature more than the allowed limits
sec
600
1
89 MaxFiltri
Filter max. control signal value
%
100
1
8 - CONTROL
8.11 UNIT PARAMETERS FOR THE INSTALLER USE
ATTENTION
The access to parameters or modifications are allowed only to the installer who assumes all responsibility, in case of doubts please
contact Airwell.
For any changes not permitted or not approved by Airwell, the same declines any responsibility for malfunctions and/or damages to
the unit/system.