8 - CONTROL
ALARMS
The code
C
indicates the presence of an anomalous situation that does not prejudice the operation of the unit.
The
E
code indicates alarms that compromise the unit operating.
The passage from a code
C
to a code
E
occurs if the alarm switches from an automatic to a manual reset, this because the number of events per hour
that occurred exceeded the critical threshold.
A
the alarm automatically resets when the cause that set it off ends
B
the alarm manually resets when the cause that set it off ends and a keypad reset is executed
Alarm
Description
Possible cause
C38
Modulating resi stance On with recovery circuit
Off
Air preheating, no anomaly
A
C39
Control of the supply title not satisfied
The unit operates regularly.
High supply air humidity: open windows, lots of people, etc.
A
E40
Inconsistency of the temperature differential
The temperature difference at the air inlet and outlet is not consistent with the
mode.
The unit can not heat / cool of 3 ° C the air introduced in the room.
Check :
-
Button action (DSG) to protect the compressor
-
Unit partially discharged of gas
-
Compressor not operating
-
4-way valve not operating
M
C65
Communication failure
as E00
A