Working procedure

(1) Install the attached drain hose to the drain port of the body. Install the hose band from 

the top of the hose within the graphic display area. Secure 

fi

 rmly with the hose band. 

(2) Use vinyl adhesive agent to glue the drain piping (PVC pipe (Ø 3/4 in. [I.D.]; Ø 1-1/16 

in. [O.D.])) which is prepared on site or elbow socket.

  (Apply color adhesive agent evenly until the gauge line and seal)

(3) Check the drainage. (See separate diagram)

(4) Install the heat insulation.

(5) Use the attached heat insulation to insulate the drain port and band parts of the body.

Install the knob 

faces upward

Attached drain hose 

heat insulation 

(Accessories)

Locally arranged 

vinyl pipe

Attached drain hose 

(Accessories)

Attached hose band

(Accessories)

Attached heat insulation

(Accessories)

3/16 to 3/8 in. 

(5 to 10 mm)

13/16 in. 

(20 mm)

Hose Band

(a) Top view

(b) Side view

(c) Top view

(d) Hose opening view

1-3/8 in.

(35 mm)

Applying area 
of adhesive 

Ø 3/4 in. [I.D.];

Ø 1-1/16 in. [O.D.]

Gauge line

3/16 in. (4 mm) or less

Make sure there are no gaps

Wind the attached heat insulation 
around the hose band

Make sure the
alignment is on top

Note: Check for drainage

Pour about 1 liter of water from the position shown in the diagram or from the air

fl

 ow 

outlet to the dew tray. Check for any abnormalities such as strange noises and whether 
the drain pump functions normally.

6. ELECTRICAL WIRING

 

WARNING

Electrical work must be performed in accordance with this Manual by a person 
certi

fi

 ed under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit. 
An insuf

fi

 cient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or 

fi

 re.

Before starting work, check that power is not being supplied to the all units.

For wiring, use the prescribed type of cables, connect them securely, making sure 
that there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as 
overheating the terminals, electric shock, or 

fi

 re.

Securely install the electrical box cover on the unit. 
An improperly installed electrical box cover can cause serious accidents such as 
electric shock or 

fi

 re through exposure to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

Use the included connection cables and power cables or ones specified by the 
manufacturer. Improper connections, insufficient insulation, or exceeding the 
allowable current can cause electric shock or 

fi

 re.

Do not modify the power cables, use extension cables, or use any branches in the 
wiring. Improper connections, insufficient insulation, or exceeding the allowable 
current can cause electric shock or 

fi

 re.

Match the terminal block numbers and connection cable colors with those of the 
outdoor unit (or RB unit). Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends 
of the wiring, can cause a malfunction, electric shock, or 

fi

 re.

Always fasten the outside covering of the connection cable with the cable clamp. (If 
the insulator is chafed, electric discharge may occur.)

We suggest installing GFEB breakers or follow local electrical code. When installing 
this system, install using ground fault equipment breakers (GFEB) to reduce the risk 
of  leaking current which result in electric shock or potential 

fi

 re.

Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly quali

fi

 ed persons in order to avoid a hazard.

 

CAUTION

Earth (Ground) the unit. 
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote control cable to-
gether. Separate these cable by 2 in. (50 mm) or more. Bundling these cables together 
will cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of the 
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor units for more than 10 seconds to discharge static 

electricity charged in the body.

• Do not touch terminals of parts and patterns implemented on PCB.

9371022314-03_IM.indb   Sec1:7

9371022314-03_IM.indb   Sec1:7

10/23/2013   2:59:35 PM

10/23/2013   2:59:35 PM

Содержание AUUB18TLAV

Страница 1: ...authorized service personnel only Français MANUEL D INSTALLATION APPAREIL INTÉRIEUR type cassette Pour le personnel agréé uniquement AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Español MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo casete Únicamente para personal de servicio autorizado ...

Страница 2: ... valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the cu...

Страница 3: ...llation Manual in a safe place and do not discard any other accessories until the installation work has been completed Name and Shape Q ty Application Operation Manual 1 Installation Manual 1 This book Cable tie Large 4 For fixing the connection pipe Large and Small Cable tie Medium 2 For transmission and remote controller cable binding Coupler heat insulation Small 1 For indoor side pipe joint Sm...

Страница 4: ...iling Function setting H in mm AUUB18 AUUB24 AUUB30 AUUB36 Standard mode 118 3 000 118 3 000 125 3 200 125 3 200 High Ceiling mode 137 3 500 137 3 500 141 3 600 165 4 200 Be sure to make the function settings with the remote controller according to the installed ceiling height Discharge Direction Setting The discharge direction can be selected as shown below 4 DIRECTION 3 DIRECTION 4 in 100 mm or ...

Страница 5: ...o M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install the hanging bolts at a place where they would be capable of holding a weight of at least 110 lbf 490 N per bolt Hole in anchor Hole in plug Concrete Insert Hanging bolt M10 Field supply 3 3 3 Body installation 1 Install the attached washer and nut prepared on site onto the hanging b...

Страница 6: ...ed humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 68 F 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tighten...

Страница 7: ...ulation After installing the Coupler heat insulation wrap both ends with vinyl tape so that there is no gap Cable tie Large Accessories Body Be sure to overlap the insulation Coupler heat insulation Coupler heat insulation Accessories No gap CAUTION Must fit tightly against body without any gap 5 INSTALLING DRAIN PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occur...

Страница 8: ...es or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection...

Страница 9: ...22 AWG 0 33 mm LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 026 in 0 65 mm Remote controller cable 2 wire type 22 AWG to 16 AWG 0 33 mm to 1 25 mm Sheathed PVC cable Non polar 2 core Remote controller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method EXAMPLE Outdoor unit or RB unit 1 Transmission Transmission Pow...

Страница 10: ...rew Power supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Shielded wire no film 1 9 16 in 40 mm 1 3 16 in 30 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cables are attached GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the speci...

Страница 11: ...using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension depending o...

Страница 12: ...ut signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF Normal In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON ...

Страница 13: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Страница 14: ...emote controller The remote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 Refer to 7 1 Setting the address for indoor unit address and refrigerant circuit ad dress settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so m...

Страница 15: ...a ture 2 Operating temperature switching of external heaters 62 00 Setting 0 Sets the temperature conditions when the external heater is ON For the temperature conditions see Temperature conditions when the external heater is ON For a more detailed explanation see the Design Technical Manual 01 Setting 1 02 Setting 2 03 Setting 3 04 Setting 4 05 Setting 5 Temperature conditions when the external h...

Страница 16: ... Does water drain easily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage...

Страница 17: ...e Error icon Touch the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller Touch the Next Page or previous page to switch to other indoor unit information ...

Отзывы: