background image

En-13

Table A

Address

Rotary Switch 

Setting

Address

Rotary Switch Setting

Refrigerant 

circuit

REF AD SW

Indoor unit

IU AD SW

× 10

× 1

× 10

× 1

0

0

0

0

0

0

1

0

1

1

0

1

2

0

2

2

0

2

3

0

3

3

0

3

4

0

4

4

0

4

5

0

5

5

0

5

6

0

6

6

0

6

7

0

7

7

0

7

8

0

8

8

0

8

9

0

9

9

0

9

10

1

0

10

1

0

11

1

1

11

1

1

12

1

2

12

1

2

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

99

9

9

63

6

3

Do not set the indoor unit address (IU AD SW) at 64 to 99. 
It may result in failure.

(3)  Remote controller address

i) 3-wire type

  Rotary switch (RC AD SW)...Factory setting “0”

  When connecting multiple indoor units to 1 standard wired remote controller, set the 

address at RC AD SW in sequence from 0.

Setting

Setting range

Type of switch

Remote controller 

address

0 to 15

Setting 

example 

0

RC AD

 

Example

  If 4 indoor units are connected.

RC AD SW

0

RC AD SW

1

RC AD SW

2

RC AD SW

3

Indoor unit

Remote 
controller

Indoor unit

Indoor unit

Indoor unit

RC AD SW

0

1

2

3

4

5

6

7

Address

0

1

2

3

4

5

6

7

RC AD SW

8

9

A

B

C

D

E

F

Address

8

9

10

11

12

13

14

15

ii) 2-wire type

  Rotary switch (RC AD SW)...Factory setting “0”
  Since the remote controller address settings are automatically con

fi

 gured, you do not 

need to con

fi

 gure them.

 If 

con

fi

 guring manually, it is necessary to con

fi

 gure both the indoor unit and the remote 

controller. For details, please refer to the remote controller manual.

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.

Indoor 
unit

Remote 
controller

Confusion

Code change

Custom code setting for indoor unit

Set the DIP switch SET 3 SW1, SW2, referring to the Table B.

SW

1

SW

2

SW

3

SW

4

DIP switch “SET 3”

ON

OFF

Table B

Custom code

A (Factory setting)

B

C

D

DIP switch SET 3 SW1

OFF

ON

OFF

ON

DIP switch SET 3 SW2

OFF

OFF

ON

ON

7.3. Function setting

•  FUNCTION SETTING can be performed with the wired or wireless remote controller.
  (The remote controller is optional equipment)
•  Refer to the wired or wireless remote controller manual for detailed setting information. 

(Set IU AD, REF AD SW to 0)

•  Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit ad-

dress settings.

•  Turn the power of the indoor unit ON before starting the setting.

* Turning on the power to the indoor units initializes EEV, so make sure the piping air 

tight test and vacuuming have been conducted before turning on the power.

* Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 
number

Setting number

Default

Details

Filter indica-

tor interval

11

00

Standard

Adjust the 

fi

 lter cleaning interval 

notification. If the notification 
is too early, change to setting 
01. If the noti

fi

 cation is too late, 

change to setting 02.

01

Longer

02

Shorter

Filter indica-

tor action

13

00

Enable

Enable or disable the 

fi

 lter indi-

cator. Setting 02 is for use with 
a central remote controller.

01

Disable

02

Display only on 

central remote 

controller

Ceiling 

air

fl

 ow

20

00

Standard

Regulate the air

fl

 ow  according 

to the needs of the installation 
location. When set to 01, the air 

fl

 ow will be stronger. (Cassette 

type only)

01

High Ceiling

Vertical 

air

fl

 ow 

direction

23

00

Standard

Adjust the vertical air

fl

 ow direc-

tion. All air

fl

 ow direction louvers 

are adjusted together.
(Cassette type only)

01

Raise

Cool air 

temperature 

trigger

30

00

Standard

Adjust the cool air trigger tem-
perature. To lower the trigger 
temperature, use setting 01. To 
raise the trigger temperature, 
use setting 02.

01

Adjust (1)

02

Adjust (2)

Heat air 

temperature 

trigger

31

00

Standard

Adjust the heat air trigger tem-
perature. To lower the trigger 
temperature by 11 degrees F (6 
degrees C), use setting 01. To 
lower the trigger temperature by 
7 degrees F (4 degrees C), use 
setting 02. To raise the trigger 
temperature, use setting 03.

01

Adjust (1)

02

Adjust (2)

03

Adjust (3)

Auto restart

40

00

Enable

Enable or disable automatic 
system restart after a power 
outage.

01

Disable

9371022314-03_IM.indb   Sec1:13

9371022314-03_IM.indb   Sec1:13

10/23/2013   2:59:38 PM

10/23/2013   2:59:38 PM

Содержание AUUB18TLAV

Страница 1: ...authorized service personnel only Français MANUEL D INSTALLATION APPAREIL INTÉRIEUR type cassette Pour le personnel agréé uniquement AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Español MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo casete Únicamente para personal de servicio autorizado ...

Страница 2: ... valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the cu...

Страница 3: ...llation Manual in a safe place and do not discard any other accessories until the installation work has been completed Name and Shape Q ty Application Operation Manual 1 Installation Manual 1 This book Cable tie Large 4 For fixing the connection pipe Large and Small Cable tie Medium 2 For transmission and remote controller cable binding Coupler heat insulation Small 1 For indoor side pipe joint Sm...

Страница 4: ...iling Function setting H in mm AUUB18 AUUB24 AUUB30 AUUB36 Standard mode 118 3 000 118 3 000 125 3 200 125 3 200 High Ceiling mode 137 3 500 137 3 500 141 3 600 165 4 200 Be sure to make the function settings with the remote controller according to the installed ceiling height Discharge Direction Setting The discharge direction can be selected as shown below 4 DIRECTION 3 DIRECTION 4 in 100 mm or ...

Страница 5: ...o M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install the hanging bolts at a place where they would be capable of holding a weight of at least 110 lbf 490 N per bolt Hole in anchor Hole in plug Concrete Insert Hanging bolt M10 Field supply 3 3 3 Body installation 1 Install the attached washer and nut prepared on site onto the hanging b...

Страница 6: ...ed humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 68 F 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tighten...

Страница 7: ...ulation After installing the Coupler heat insulation wrap both ends with vinyl tape so that there is no gap Cable tie Large Accessories Body Be sure to overlap the insulation Coupler heat insulation Coupler heat insulation Accessories No gap CAUTION Must fit tightly against body without any gap 5 INSTALLING DRAIN PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occur...

Страница 8: ...es or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection...

Страница 9: ...22 AWG 0 33 mm LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 026 in 0 65 mm Remote controller cable 2 wire type 22 AWG to 16 AWG 0 33 mm to 1 25 mm Sheathed PVC cable Non polar 2 core Remote controller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method EXAMPLE Outdoor unit or RB unit 1 Transmission Transmission Pow...

Страница 10: ...rew Power supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Shielded wire no film 1 9 16 in 40 mm 1 3 16 in 30 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cables are attached GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the speci...

Страница 11: ...using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension depending o...

Страница 12: ...ut signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF Normal In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON ...

Страница 13: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Страница 14: ...emote controller The remote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 Refer to 7 1 Setting the address for indoor unit address and refrigerant circuit ad dress settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so m...

Страница 15: ...a ture 2 Operating temperature switching of external heaters 62 00 Setting 0 Sets the temperature conditions when the external heater is ON For the temperature conditions see Temperature conditions when the external heater is ON For a more detailed explanation see the Design Technical Manual 01 Setting 1 02 Setting 2 03 Setting 3 04 Setting 4 05 Setting 5 Temperature conditions when the external h...

Страница 16: ... Does water drain easily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage...

Страница 17: ...e Error icon Touch the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller Touch the Next Page or previous page to switch to other indoor unit information ...

Отзывы: