En-2

2.  ABOUT THIS PRODUCT

2.1. Precautions for using the R410A refrigerant

 

WARNING

Do not introduce any substance other than the prescribed refrigerant into the 
refrigeration cycle. 
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become 
abnormally high and cause the piping to rupture.

If there is a refrigerant leakage, make sure that it does not exceed the concentration 
limit. 
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such 
as oxygen starvation.

Do not touch refrigerant that has leaked from the refrigerant pipe connections or other 
area. Touching the refrigerant directly can cause frostbite.

If a refrigerant leakage occurs during operation, immediately vacate the premises and 
thoroughly ventilate the area. 
If the refrigerant comes in contact with a 

fl

 ame, it produces a toxic gas.

2.2. Special tool for R410A

 

WARNING

To install a unit that uses the R410A refrigerant, use dedicated tools and piping 
materials that have been manufactured speci

fi

 cally for R410A use. 

Because the pressure of the R410A refrigerant is approximately 1.6 times higher 
than the R22, failure to use dedicated piping material or improper installation can 
cause rupture or injury. 
Furthermore, it can cause serious accidents such as water leakage, electric shock, 
or 

fi

 re.

Tool name

Contents of change

Gauge manifold

Pressure is huge and cannot be measured with a conventional 
(R22) gauge. To prevent erroneous mixing of other refrigerants, 
the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high pressure 
display range 30 in.Hg to 768 psi (–0.1 to 5.3 MPa) and a low 
pressure display range 30 in.Hg to 551 psi (–0.1 to 3.8 MPa).

Charging hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional (R22) vacuum pump can be used by installing 
a vacuum pump adapter. Be sure that the pump oil does not 
backflow into the system. Use one capable for vacuum suction 
of 5 Torr, –755 mm Hg (–100.7 kPa).

Gas leakage 

detector

Special gas leakage detector for HFC refrigerant R410A.

2.3. Accessories

 

WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or 
other prescribed parts. 
The use of non-prescribed parts can cause serious accidents such as the unit to fall, 
water leakage, electric shock, or 

fi

 re.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other 
accessories until the installation work has been completed.

Name and Shape

Q’ty

Application

Operation Manual

1

Installation Manual

1

(This book)

Cable tie (Large)

4

For 

fi

 xing the connection 

pipe (Large and Small)

Cable tie (Medium)

2

For transmission and remote 
controller cable binding.

Coupler heat insulation 
(Small)

1

For indoor side pipe joint (Small)

Coupler heat insulation 
(Large)

1

For indoor side pipe joint (Large)

Template (Carton top)

1

For installing indoor unit.

Washer

8

For installing indoor unit.

Drain hose insulation

1

For installing drain hose

Drain Hose

1

For installing drain pipe
(Ø 3/4 in. [I.D.]; Ø 1-1/16 in. [O.D.])

Hose Band

1

For installing drain hose

Drain Pipe Insulation

1

For installing drain pipe

2.4. Optional parts

Description

Model

Application

External connect kit

UTY-XWZXZC

For output function

(Output terminal / CNB01)

UTY-XWZXZB

For control input function

(Apply voltage terminal / CNA01)

UTY-XWZXZD

For control input function

(Dry contact terminal / CNA02)

UTY-XWZXZ7

For forced thermostat off function

(Apply voltage terminal / CNA03)

UTY-XWZXZE

For forced thermostat off function

(Dry contact terminal / CNA04)

2.5. About unit of the length

All Fujitsu General products are manufactured to metric units and tolerances. United 
States customary units are provided for reference only. In cases where exact dimensions 
and tolerances are required, always refer to metric units.

3. INSTALLATION WORK

Correct initial installation location is important because it is dif

fi

 cult to move unit after it is 

installed.

3.1. Selecting an installation location

 

WARNING

Select installation locations that can properly support the weight of the indoor. Install 
the units securely so that they do not topple or fall.

 

CAUTION

Do not install the unit in the following areas:

• Area with high salt content, such as at the seaside. 

It will deteriorate metal parts, causing the parts to fail or the unit to leak water.

• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.

• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause 
refrigerant leakage.

• Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline.

If gas leaks and settles around the unit, it can cause a 

fi

 re.

• Area where animals may urinate on the unit or ammonia may be generated.

9371022314-03_IM.indb   Sec1:2

9371022314-03_IM.indb   Sec1:2

10/23/2013   2:59:30 PM

10/23/2013   2:59:30 PM

Содержание AUUB18TLAV

Страница 1: ...authorized service personnel only Français MANUEL D INSTALLATION APPAREIL INTÉRIEUR type cassette Pour le personnel agréé uniquement AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Español MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo casete Únicamente para personal de servicio autorizado ...

Страница 2: ... valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the cu...

Страница 3: ...llation Manual in a safe place and do not discard any other accessories until the installation work has been completed Name and Shape Q ty Application Operation Manual 1 Installation Manual 1 This book Cable tie Large 4 For fixing the connection pipe Large and Small Cable tie Medium 2 For transmission and remote controller cable binding Coupler heat insulation Small 1 For indoor side pipe joint Sm...

Страница 4: ...iling Function setting H in mm AUUB18 AUUB24 AUUB30 AUUB36 Standard mode 118 3 000 118 3 000 125 3 200 125 3 200 High Ceiling mode 137 3 500 137 3 500 141 3 600 165 4 200 Be sure to make the function settings with the remote controller according to the installed ceiling height Discharge Direction Setting The discharge direction can be selected as shown below 4 DIRECTION 3 DIRECTION 4 in 100 mm or ...

Страница 5: ...o M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install the hanging bolts at a place where they would be capable of holding a weight of at least 110 lbf 490 N per bolt Hole in anchor Hole in plug Concrete Insert Hanging bolt M10 Field supply 3 3 3 Body installation 1 Install the attached washer and nut prepared on site onto the hanging b...

Страница 6: ...ed humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 68 F 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tighten...

Страница 7: ...ulation After installing the Coupler heat insulation wrap both ends with vinyl tape so that there is no gap Cable tie Large Accessories Body Be sure to overlap the insulation Coupler heat insulation Coupler heat insulation Accessories No gap CAUTION Must fit tightly against body without any gap 5 INSTALLING DRAIN PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occur...

Страница 8: ...es or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection...

Страница 9: ...22 AWG 0 33 mm LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 026 in 0 65 mm Remote controller cable 2 wire type 22 AWG to 16 AWG 0 33 mm to 1 25 mm Sheathed PVC cable Non polar 2 core Remote controller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method EXAMPLE Outdoor unit or RB unit 1 Transmission Transmission Pow...

Страница 10: ...rew Power supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Shielded wire no film 1 9 16 in 40 mm 1 3 16 in 30 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cables are attached GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the speci...

Страница 11: ...using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension depending o...

Страница 12: ...ut signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF Normal In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON ...

Страница 13: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Страница 14: ...emote controller The remote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 Refer to 7 1 Setting the address for indoor unit address and refrigerant circuit ad dress settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so m...

Страница 15: ...a ture 2 Operating temperature switching of external heaters 62 00 Setting 0 Sets the temperature conditions when the external heater is ON For the temperature conditions see Temperature conditions when the external heater is ON For a more detailed explanation see the Design Technical Manual 01 Setting 1 02 Setting 2 03 Setting 3 04 Setting 4 05 Setting 5 Temperature conditions when the external h...

Страница 16: ... Does water drain easily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage...

Страница 17: ...e Error icon Touch the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller Touch the Next Page or previous page to switch to other indoor unit information ...

Отзывы: