background image

En-6

4.3.3. Pipe connection 

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit 
correctly. If the centering is improper, the 

fl

 are nut cannot tightened smoothly. If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before 
connecting the connection pipe.

Do not use mineral oil on 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 
tighten the 

fl

 are nut correctly.

(1) Detach the caps and plugs from the pipes.

(2) Center the pipe against the port on the indoor unit,  and then turn the 

fl

 are nut by 

hand.

 

Connection pipe (Gas)

Connection pipe 
(Liquid)

(3) When  the 

fl

 are nut is tightened properly by your hand, hold the body side coupling 

with a separate spanner, then tighten with a torque wrench. (See the table below for 
the 

fl

 are nut tightening torques.)

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Indoor unit pipe 
(Body side)

Torque wrench

Flare nut [in. (mm)]

Tightening torque [lbf·ft. (N·m)]

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

4.4. Installing heat insulation

 

CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), 
perform this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to 
do so may cause water leaks.

After checking for gas leaks, insulate by wrapping insulation around the 2 parts (gas and 
liquid) of the indoor unit coupling, using the Coupler heat insulation.
After installing the Coupler heat insulation, wrap both ends with vinyl tape so that there is 
no gap.

Cable tie (Large) 
(Accessories)

Body

Be sure to overlap 
the insulation

Coupler heat  
insulation

Coupler heat 
insulation

(Accessories)

No gap

 

CAUTION

Must 

fi

 t tightly against body without any gap.

5.  INSTALLING DRAIN PIPES

 

WARNING

Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat 
exchange erosion may occur)

Insulate the parts properly so that water will not drip from the connection parts.

Check for proper drainage after the construction by using the visible portion of 
transparent drain port and the drain piping 

fi

 nal outlet on the body.

 

CAUTION

Do not apply adhesive agent on the drain port of the body. (Use the attached drain 
hose and connect the drain piping)

• Install the drain pipe with downward gradient (1/100 to 1/50) and so there are no rises 

or traps in the pipe. Unsmooth draining caused by accumulated water 

fl

 ow in the pipe 

may cause clogged drain.

• Use general hard polyvinyl chloride pipe (Ø 3/4 in. [I.D.]; Ø 1-1/16 in. [O.D.]).
• When the pipe is long, install supporters.
• Do not perform air bleeding. Drainage may be blown out.
• Always heat insulate the indoor side of the drain pipe.
• If it is impossible to have suf

fi

 cient gradient of pipe, perform drain lift-up.

Pipe size

Drain pipe

Ø 3/4 in. [I.D.]; Ø 1-1/16 in. [O.D.] 

Hanging 

fi

 ttings

60 to 78 in. (1.5 to 2.0 m)

Ø 3/4 in. [I.D.]; Ø 1-1/16 in. [O.D.]
Downward gradient 1/100 to 1/50

Rise

PROHIBITED:

Trap

Air bleeding

When lifting up drain:
• Height of inclined pipe should be less than 33 in. (850 mm) from the ceiling. A rise 

dimension over this range will cause leakage.

• Lift up the pipe vertically at the position of 11 in. (300 mm) or less from the unit.

11 in. (300 mm) or less

Ø 3/4 in. [I.D.]; 
Ø 1-1/16 in. [O.D.]
local arrangement

33 in. 
(850 mm) or less

Horizontal or 
upward gradient

Downward gradient 
1/100 to 1/50

Ø 1 in. [I.D.]; Ø 1-5/16 in. [O.D.] or more
Downward gradient 1/100 to 1/50

33 in. (850 mm) 
or less

9371022314-03_IM.indb   Sec1:6

9371022314-03_IM.indb   Sec1:6

10/23/2013   2:59:34 PM

10/23/2013   2:59:34 PM

Содержание AUUB18TLAV

Страница 1: ...authorized service personnel only Français MANUEL D INSTALLATION APPAREIL INTÉRIEUR type cassette Pour le personnel agréé uniquement AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Español MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo casete Únicamente para personal de servicio autorizado ...

Страница 2: ... valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the cu...

Страница 3: ...llation Manual in a safe place and do not discard any other accessories until the installation work has been completed Name and Shape Q ty Application Operation Manual 1 Installation Manual 1 This book Cable tie Large 4 For fixing the connection pipe Large and Small Cable tie Medium 2 For transmission and remote controller cable binding Coupler heat insulation Small 1 For indoor side pipe joint Sm...

Страница 4: ...iling Function setting H in mm AUUB18 AUUB24 AUUB30 AUUB36 Standard mode 118 3 000 118 3 000 125 3 200 125 3 200 High Ceiling mode 137 3 500 137 3 500 141 3 600 165 4 200 Be sure to make the function settings with the remote controller according to the installed ceiling height Discharge Direction Setting The discharge direction can be selected as shown below 4 DIRECTION 3 DIRECTION 4 in 100 mm or ...

Страница 5: ...o M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install the hanging bolts at a place where they would be capable of holding a weight of at least 110 lbf 490 N per bolt Hole in anchor Hole in plug Concrete Insert Hanging bolt M10 Field supply 3 3 3 Body installation 1 Install the attached washer and nut prepared on site onto the hanging b...

Страница 6: ...ed humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 68 F 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tighten...

Страница 7: ...ulation After installing the Coupler heat insulation wrap both ends with vinyl tape so that there is no gap Cable tie Large Accessories Body Be sure to overlap the insulation Coupler heat insulation Coupler heat insulation Accessories No gap CAUTION Must fit tightly against body without any gap 5 INSTALLING DRAIN PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occur...

Страница 8: ...es or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection...

Страница 9: ...22 AWG 0 33 mm LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 026 in 0 65 mm Remote controller cable 2 wire type 22 AWG to 16 AWG 0 33 mm to 1 25 mm Sheathed PVC cable Non polar 2 core Remote controller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method EXAMPLE Outdoor unit or RB unit 1 Transmission Transmission Pow...

Страница 10: ...rew Power supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Shielded wire no film 1 9 16 in 40 mm 1 3 16 in 30 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cables are attached GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the speci...

Страница 11: ...using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension depending o...

Страница 12: ...ut signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF Normal In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON ...

Страница 13: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Страница 14: ...emote controller The remote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 Refer to 7 1 Setting the address for indoor unit address and refrigerant circuit ad dress settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so m...

Страница 15: ...a ture 2 Operating temperature switching of external heaters 62 00 Setting 0 Sets the temperature conditions when the external heater is ON For the temperature conditions see Temperature conditions when the external heater is ON For a more detailed explanation see the Design Technical Manual 01 Setting 1 02 Setting 2 03 Setting 3 04 Setting 4 05 Setting 5 Temperature conditions when the external h...

Страница 16: ... Does water drain easily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage...

Страница 17: ...e Error icon Touch the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller Touch the Next Page or previous page to switch to other indoor unit information ...

Отзывы: