En-10
CAUTION
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
SW1
2WIRE
3WIRE
Lock nut
Conduit connector
(L1, L2 (N): Power
supply cable)
X1, X2:
Transmission cable
Cable tie (Medium)
(Accessories)
Y1,Y2,Y3:
Remote controller
cable
*1:
If you connect the remote controller cable to the terminal Y3, 2-wire type
remote controller does not work.
DIP switch (SW1)
For 2-wire type
For 3-wire type
Connect the remote
controller cable
Y1: Non-polar
Y2: Non-polar
Y3: Do not connect *1
Y1: Red
Y2: White
Y3: Black
Set the DIP switch (SW1)
2WIRE (Factory setting)
3WIRE
Earth (Ground)
(3) Install the wiring cover and control box cover.
CAUTION
Do not bundle the remote controller cable, or wire the remote controller cable in
parallel, with the indoor unit connection wire (to the outdoor unit) and the power
supply cable. It may cause erroneous operation.
Fix the conduit with the supporters as shown below.
•
Conduit (Power supply cable)
Supporter
Indoor unit
30 in.
(756 mm)
or less
54 in.
(1,361 mm)
or less
54 in.
(1,361 mm)
or less
54 in.
(1,361 mm)
or less
1
6.5. External input and external output (Optional
parts)
CAUTION
Do not operate any switches other than prescribed, as it can cause the unit to operate
improperly or malfunction.
Use an insulated screwdriver to set the DIP switches.
Apply voltage terminal
(CNA03)
(CNA01)
(CNA04)
(CNA02)
Dry contact terminal
Output terminal
(CNB01)
Controller PCB
DIP switch
(SET 2)
OFF
SW1
SW2
SW3
SW4
ON
(1) External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 492 ft. (150
m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
●
Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Input
de
vic
e 1
Input
de
vic
e 2
Input
de
vic
e 3
Load
resistance
Load
resistance
Load
resistance
*1
DC power supply
12 to 24V
connected unit
*a
*a
*a
P.C.B
CNA01
CNA03
*b
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power supply
12 to 24V
connected unit
Load
resistance
P.C.B
P.C.B
CNA01
P.C.B
Input
de
vic
e 1
Input
de
vic
e 2
Indo
or
unit
Indo
or
unit
Indo
or
unit
Load
resistance
CNA01
CNA01