En-9
Operation behavior
• Input signal type
The input signal type can be selected.
Pulse
Edge
The width of pulse
must be longer than
200 msec.
It is switched by Dip-sw on the indoor
unit PCB.
Dip-sw [Set 2-2]
Input signal type
OFF
Edge
ON
Pulse
• When function setting is “Start/Stop” mode
In the case of “Edge” input
Connector
Input signal
Command
Ch1 of CN6 or CN17
OFF
→
ON
Operation
ON
→
OFF
Stop
In the case of “Pulse” input
Connector
Input signal
Command
CN6 or CN17
Ch1
OFF
→
ON
Operation
Ch2
OFF
→
ON
Stop
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
• When function setting is “Emergency stop” mode
In the case of “Edge” input
Connector
Input signal
Command
Ch1 of CN6 or CN17
OFF
→
ON
Emergency stop
ON
→
OFF
Normal
In the case of “Pulse” input
Connector
Input signal
Command
CN6 or CN17
Ch1
OFF
→
ON
Emergency stop
Ch2
OFF
→
ON
Normal
* All indoor units of same refrigerant system stops when Emergency stop operates.
• When function setting is “Forced stop” mode
In the case of “Edge” input
Connector
Input signal
Command
Ch1 of CN6 or CN17
OFF
→
ON
Forced stop
ON
→
OFF
Normal
In the case of “Pulse” input
Connector
Input signal
Command
CN6 or CN17
Ch1
OFF
→
ON
Forced stop
Ch2
OFF
→
ON
Normal
* When the forced stop is triggered, indoor unit stops and Start/Stop operation by a
remote controller is restricted.
CAUTION
When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Start/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected with
function setting of indoor unit.
*1 Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.
*a The allowable current is DC 5~10 mA. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3.
Connect
correctly.
When connected to voltage terminals of multiple indoor units with a connected unit, be
sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power
supply 12-24 V
Connected unit
Load
resistance
P.C.B
P.C.B
CN6
CN6
CN6
P.C.B
In
pu
t d
ev
ic
e 1
In
pu
t d
ev
ic
e 2
Indo
or
unit
Indo
or
unit
Indo
or
unit
Load
resistance
• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device you want to connect, use the no
voltage terminal ([CN17]).
1
2
3
P.C.B
GND
Ch 1
*c
*c
*d
Ch 2
CN17
Connected unit
*c Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d The wiring is different from voltage terminals. Be suf
fi
ciently careful when wiring.
When connected to no voltage terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
When connected to multiple indoor units directly, it will cause breakdown.
Po
w
e
r s
u
p
p
ly
f
o
r r
e
la
y
Indo
or
unit
Indo
or
unit
Indo
or
unit
Input device 2
Input device 1
K1~K6: Relay
(Device for DC Current)
P.C.B
K1
P.C.B
P.C.B
CN17
CN17
CN17
K2
K3
K4
K5
K6
9373370154-01_IM.indb 9