background image

En-6

When the power crossover wiring is done, make it so that the total of the MCA of the con-
nected indoor equipment does not exceed the 15 A.

B. Earth leakage breaker requirements

Breaker capacity

Maximum connectable indoor unit

30 mA, 0.1 sec or less

8

100 mA, 0.1 sec or less

27

200 mA, 0.1 sec or less

39 (Upper limit of the refrigerant system)

If the number of units of connected indoor unit exceeds the upper limit, either add breakers 
or use a breaker with large capacitance.

1

6.1.1 Transmission and remote controller wiring speci

fi

 cations

Follow the speci

fi

 cations below for the transmission and remote controller cable.

Cable size

Wire type

Remarks

Transmission cable

22 AWG

(0.33 mm²)

LEVEL 4 (NEMA)

non-polar 2 core, twisted 

pair solid core diam-

eter 1/32 in. (0.65 mm)

LONWORKS 

®

compatible cable

Remote control-

ler cable

22 AWG

(0.33 mm²)

Sheathed PVC cable

Polar 3 core 
Twisted pair

1

6.2. Wiring method

EXAMPLE

Breaker 1 :   Earth leakage breaker 

(GFEB)

Breaker 2 :   Current breaker 

(MOP breaker)

Outdoor unit

Power supply

Breaker 1

Breaker 2

Transmission

Power supply

Indoor unit

Indoor unit

Indoor unit

Transmission

Power 

supply

Remote 

control

Transmission

Power 

supply

Remote 

control

Transmission

Power 

supply

Remote 

control

Breaker 2

Breaker 2

Breaker 2

Breaker 1

Breaker 1

Breaker 1

Power supply

Remote 

controller 

(Master)

Power supply

Remote 

controller 

(Slave)

Power supply

Remote 

controller

Crossover wiring of power supply

Indoor unit

Indoor unit

Indoor unit

Power 

supply

Remote 

control

Power 

supply

Remote 

control

Power 

supply

Remote 

control

Pull box

Pull box

Breaker 1

Breaker 2

Power supply

Remote 

controller 

(Master)

Remote 

controller 

(Slave)

Remote 

controller

6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Conduit connector

Earth 
(ground) wire

6-11/16 in. (170 mm)

6-7/8 in. (175 mm)

1-3/8 in. (35 mm)

31/32 in. (25 mm)

For U.S.A. and Canada

For Others

Earth 
(ground) wire

Conduit holder

6. ELECTRICAL WIRING

]

 WARNING

Electrical work must be performed in accordance with this Manual by a person certi

fi

 ed 

under the national or regional regulations. Be sure to use a dedicated circuit for the unit. 

An insuf

fi

 cient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or 

fi

 re.

Before starting work, check that power is not being supplied to the indoor unit and 

outdoor unit.

Use the included connection cables and power cables or ones specified by the 

manufacturer. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

For wiring, use the prescribed type of cables, connect them securely, making sure that there are no 

external forces of the cables applied to the terminal connections. Improperly connected or secured 

cables can cause serious accidents such as overheating the terminals, electric shock, or 

fi

 re.

Do not modify the power cables, use extension cables, or use any branches in the 

wiring. Improper connections, insufficient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

Match the terminal board numbers and connection cable colors with those of the 

outdoor unit. Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 

cables with wiring holders. Improper connections, either in the wiring or at the ends of the 

wiring, can cause a malfunction, electric shock, or 

fi

 re.

Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric discharge may occur.)

Securely install the electrical box cover on the unit. An improperly installed electrical 

box cover can cause serious accidents such as electric shock or 

fi

 re through exposure 

to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 

could result.

For U.S.A. and Canada:

When installing this system in high humidity locations, install using ground fault equipment 

breakers (often referred to in other countries as an ELCB earth leakage current breaker) 

to reduce the risk of  leaking current which result in electric shock or potential 

fi

 re.

For others:

Install an earth (ground) leakage breaker. In addition, install the earth (ground) 

leakage breaker so that the entire AC main power supply is cut off at the same time. 

Otherwise, electric shock or 

fi

 re could result.

Always connect the earth (ground) cable.

Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.

Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

If the supply cord is damaged, it must be replaced by the manufacturer, its service 

agent or similarly quali

fi

 ed persons in order to avoid a hazard.

 CAUTION

Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cable to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote controller cable 
together. 
Separate these cable by 1-31/32 in. (50 mm) or more. 
Bundling these cables together will cause miss operation or breakdown.

  When handling PCB, static electricity charged in the body may cause malfunction of 

the PCB. Follow the cautions below:
•  Establish an earth (ground) for the indoor and outdoor units and peripheral devices.

•  Cut power (breaker) off.
•  Touch metal part of the indoor and outdoor units for more than 10 seconds to 

discharge static electricity charged in the body.

•  Do not touch terminals of parts and patterns implemented on PCB.

1

6.1. Electrical requirement

Voltage rating

208/230 V

Operating range

187 to 253 V

•  Select the power cable type and size in accordance with relevant local and national 

regulations.

•  Specifications for local wiring power cord and branch wiring are in compliance with local code.
•  Select the correct cable type and size according to the country or region’s 

regulations.

•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 

wire diameter when the wire length is long.

Refer to the table for the breaker specifications of each installation condition. Perform the 
power crossover wiring within the range of the same refrigerant system. When the crossover 
wiring is done, make a connection for indoor unit to satisfy conditions A and B below.

A.

 

Current breaker requirements

Model

MCA

MOP  (Fuse capacity)

ASUB18RLAV

0.40 A

20 A

ASUB24RLAV

0.63 A

MCA: Minimum Circuit Ampacity
MOP: Maximum Overcurrent Protection

9373370154-01_IM.indb   6

9373370154-01_IM.indb   6

3/14/2012   3:03:52 PM

3/14/2012   3:03:52 PM

Содержание ASUB18RLAV

Страница 1: ...ll Mounted Type APPAREIL INTÉRIEUR Type montage mural UNIDAD INTERIOR Tipo Montado en Pared UNIDADE INTERIOR Tipo montado na parede For authorized personnel only Pour le personnel agréé uniquement Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados TM PART NO 9373370154 ASUB18RLAV ASUB24RLAV ...

Страница 2: ...re opening the refrigerant valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain c...

Страница 3: ...1 For indoor unit installation Cloth tape 1 For indoor unit installation Name and Shape Q ty Application Tapping screw Big M4 25 mm 8 For wall hook bracket installa tion Air cleaning filter 2 Air cleaning filter frame 2 Drain hose Insulation 1 For installing drain hose Connecting cable 2 For wired remote controller cable connection and simple remote controller cable connection Adapter cable Remote...

Страница 4: ...wood screws after confirming using the level indicator that the clamp is horizontal WARNING Install the wall hook bracket level both horizontally and vertically If the wall hook bracket is tilted water will drip to the floor As the weight of the indoor unit is 33 to 40 lbs 15 to 18 kg it should be installed after properly examining the place where it is intended to be installed If the place is not...

Страница 5: ...imension B 0 015 0 4 in mm Flare tool for R410A clutch type 1 4 6 35 0 to 0 020 0 to 0 5 11 32 9 1 3 8 9 52 17 32 13 2 1 2 12 70 21 32 16 6 5 8 15 88 25 32 19 7 3 4 19 05 15 16 24 0 When using conventional R22 flare tools to flare R410A pipes the dimension A should be approximately 0 020 in 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring ...

Страница 6: ...t remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Instal...

Страница 7: ...es with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accide...

Страница 8: ... for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Sleeve Screw with special washer Screw with special washer Ring terminal Cable Cable Terminal block Ring terminal Ring terminal Strip 13 32 in 10 mm WARNING Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause hea...

Страница 9: ...ith appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input selection Use either one of these types of terminal according to the application Both types of termi nals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the vo...

Страница 10: ...p Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 1 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected load Do not impress a voltage exceeding 24 V across pins 1 2 and 1 3 a The allowable current is DC 5 10 mA Recommended DC 5 mA Provide a load resistan...

Страница 11: ...ctor to join field cable and wire kit wire Connect the wire with connecting wire with solder Important Be sure to insulate the connection between the wires Option parts External input output wire Insulated connection Field supply Input No Voltage terminal CN17 Controller PCB Input Voltage terminal CN6 Output terminal CN16 CN17 CN16 CN6 Connecting cables Controller PCB Cable tie Field supply 7 FIEL...

Страница 12: ...tch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigerant circuit address as the outdoor unit Setting Setting range Type of switch Indoor unit address 0 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 99 Setting example 63 REF AD 10 REF AD 1 Table A Address Rotary Swi...

Страница 13: ... 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller Horizontal swing airflow direction 24 00 Default Adjust the horizontal swing airflow direction For horizontal swing equipped mod els 01 Left half 02 Right half Cool air tem perature trigger 30 00 Default Adjust the cool air trigger tempera...

Страница 14: ...umber 2 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 11 sec 10 sec 9 sec 1 cycle 12 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF 8 FINISHING Before performing this section perform a sealing test Refer to the installation Manual for the outdoor unit 1 8 1 Connection pipe cable and drain hose Insulate the drain hose if n...

Страница 15: ...smission and Re mote controller cable Drain hose Saddle Pipe Outside wall cap Wall Outdoors Sealer putty Field supply GOOD Drain hose Saddle Lifted up Wave End in water PROHIBITED 1 8 2 Installing front cover Fix the indoor unit 1 Please remove the spacer Indoor Unit Remove Spacer 2 Hook the fittings of the indoor unit to the 2 bottom hooks while lowering the unit and pushing it against the wall B...

Страница 16: ... burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No cooling No heating Does start and stop air con ditioner operation by remote controller or external device No operation After installation is completed has the proper operation and handling been explained ...

Страница 17: ......

Отзывы: