En-7

 CAUTION

Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote controller cable 
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of 
the PCB. Follow the cautions below:

•  Establish an earth (ground) for the indoor and outdoor units and peripheral 

devices.

•  Cut power (breaker) off.

•  Touch metal part of the indoor unit for more than 10 seconds to discharge static 

electricity charged in the body.

•  Do not touch terminals of parts and patterns implemented on PCB.

6.1. Electrical requirement

Voltage rating

230 V

Operating range

198 to 264 V (50 Hz)
198 to 253 V (60 Hz)

•  Select the power cable type and size in accordance with relevant local and national 

regulations.

•  Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.
Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform 

the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MFA

ARXC36GBTH

1.50 A

20 A

MCA: Minimum Circuit Ampacity
MFA: Main Fuse Ampacity
When the power crossover wiring is done, make it so that the total of the MCA of the 
connected RB units and indoor units does not exceed the 15 A. For RB unit MCA, refer to 
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Earth leakage breaker requirements

Breaker capacity

* Maximum connectable “indoor units” or 

“indoor units + RB units”

30 mA, 0.1 sec or less

44 or less **

100 mA, 0.1 sec or less

45 to 148

*   Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
**  If the total number of units connected to the breaker exceeds 44, either add a 30mA 

breaker, or use breakers with a greater capacity.

6.1.1. Cable speci

fi

 cations

Follow the speci

fi

 cations below for the power supply, transmission and remote controller 

cable.

Recommended 

cable size (mm

2

)

Cable type

Remark

Power supply cable

2.5

Type245 IEC57 or 
equivalent

2 Cable + earth (ground)

Transmission cable

0.33

LONWORKS 
compatible cable

22 AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted 
pair solid core diameter 
0.65 mm

Remote controller cable
(2-wire type)

0.33 to 1.25

Sheathed PVC cable* Non polar 2 core

Remote controller cable
(3-wire type)

0.33

Sheathed PVC cable* Polar 3 core

*:  

Use shielded cable in accordance with local rules for remote controller cable.

6.2. Wiring method

Example

Outdoor unit or RB unit *1

Transmission

Transmission

Power supply

Breaker

Power supply

Remote controller 

(Master)

*1:  When connecting to the Heat Recovery System, refer to the installation manual of 

the RB unit.

*2: Earth (Ground) the remote controller if it has a earth (ground) cable.

*3: When connecting the 2-wire type remote controller, Y3 is not used.

Remote controller 

(Slave)

Remote controller 

Breaker

Breaker

Indoor unit

Remote 

control

*2

*2

*2

*3

*3

*3

Indoor unit

Indoor unit

(Crossover wiring of power supply)

Breaker

Indoor unit

Power supply

Pull box

Pull box

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

*  (Ground) the remote controller if it has an earth (ground) wire.

Connect the earth (ground) wire of the remote controller to the earth 
(ground) terminal of transmission.

6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure 

below.

Power supply cable

Earth (Ground) 

cable

25 mm

35 mm

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Strip 25 mm

Screw with 
special washer

Terminal block

Cable end (Loop)

Cable end (Loop)

Loop

Screw with 
special washer

Cable

Cable

9373870203_IM.indb   7

9373870203_IM.indb   7

2016/1/8   8:41:21

2016/1/8   8:41:21

Содержание ARXC36GBTH

Страница 1: ...6GBTH TM MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE...

Страница 2: ...service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING D...

Страница 3: ...unting position together with the customer as follows WARNING Select installation locations that can properly support the weight of the indoor unit Install the units securely so that they do not toppl...

Страница 4: ...G Install the air conditioner in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not...

Страница 5: ...pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break CAUTION To prevent people from touching the parts insid...

Страница 6: ...tion and the product 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe VP25 and connect it with adhesive polyvinyl chloride so that there is no leakage The position of the installed dr...

Страница 7: ...g the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable cur...

Страница 8: ...B units If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below fo...

Страница 9: ...bles are attached Fig B GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly ca...

Страница 10: ...Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correc...

Страница 11: ...onnector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input...

Страница 12: ...lation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB C...

Страница 13: ...1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting mu...

Страница 14: ...Disable Cool Air Preven tion 43 00 Super low Restrain the cold airflow with mak ing the airflow lower when starting heating operation To correspond to the ventilation set to 01 01 Follow the setting o...

Страница 15: ...unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan mo...

Отзывы: