background image

En-4

•  Use pipe with water-resistant heat insulation.

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 
cause water leaks. 
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only) 
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping. 
If the expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or 
thicker and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm 
or thicker. If heat insulation is used that is not as thick as speci

fi

 ed, condensation may 

form on the surface of the insulation. 
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less 
(at 20 °C).

4.3. Flare connection (pipe connection)

 WARNING

Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate a hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

4.3.1. Flaring

Use special 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert 

the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and respectively) 

onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use the outdoor units 

(or RB unit) special R410A 

fl

 are tool, Leakage of refrigerant may result if other 

fl

 are 

nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Check if [L] is 

fl

 ared uniformly and 

is not cracked or scratched.

Die

Pipe

A

B

Pipe outside diameter 

[mm (in)]

Dimension A [mm]

Dimension B

-

0

0.4 

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional (R22) 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.5 mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are 

tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A. 

It is recommended that a R410A 

fl

 aring tool is used.

Pipe outside

diameter [mm (in)]

Width across flats

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

4.3.2. Bending pipes

• The pipes are shaped by your hands or pipe bender. Be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
•  When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

to bend or stretch them any more. Do not bend or stretch the pipes more than 3 times.

 CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

 CAUTION

To prevent people from touching the parts inside the unit, be sure to install grilles on 
the inlet and outlet ports. The grilles must be designed in such a way that cannot be 
removed without tools.

The static pressure outside the unit is as follows.
   ARXC36 Model: 0 to 200 Pa

If an intake duct is installed, take care not to damage the temperature sensor (the 
temperature sensor is attached to the intake port 

fl

 ange).

Install the air inlet grille for air circulation. The correct temperature can not be 
detected.

Unit

Duct 

(locally purchased)

Outlet Grille (locally 

purchased)

Inlet Grille 

(locally purchased)

(Room)

When connecting the duct, perform duct-insulation that is appropriate for the installing 
environment.
Inappropriate insulation work may cause condensation on the surface of the insulating 
material, and may lead condensation drip.

Be sure to install the air 

fi

 lter in the air inlet. If the air 

fi

 lter is not installed, the heat 

exchanger may be clogged and its performance may decrease.

4. PIPE INSTALLATION

 CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant R410A models. Also, when storing the piping, securely seal the openings 
by pinching, taping, etc.

While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1. Selecting the pipe material

 CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.

Do not use copper pipes that have a collapsed, deformed, or discolored portion 
(especially on the interior surface). Otherwise, the expansion valve or capillary tube 
may become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary 
to choose adequate materials.

•  Thicknesses of copper pipes used with R410A are as shown in the table.
•  Never use copper pipes thinner than those indicated in the table even if they are 

available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [mm (in)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

4.2. Pipe requirement

 CAUTION

Refer to the Installation Manual of the outdoor unit for description of the length of 
connecting pipe or for difference of its elevation.

Width across 

fl

 ats

9373870203_IM.indb   4

9373870203_IM.indb   4

2016/1/8   8:41:20

2016/1/8   8:41:20

Содержание ARXC36GBTH

Страница 1: ...6GBTH TM MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE...

Страница 2: ...service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING D...

Страница 3: ...unting position together with the customer as follows WARNING Select installation locations that can properly support the weight of the indoor unit Install the units securely so that they do not toppl...

Страница 4: ...G Install the air conditioner in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not...

Страница 5: ...pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break CAUTION To prevent people from touching the parts insid...

Страница 6: ...tion and the product 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe VP25 and connect it with adhesive polyvinyl chloride so that there is no leakage The position of the installed dr...

Страница 7: ...g the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable cur...

Страница 8: ...B units If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below fo...

Страница 9: ...bles are attached Fig B GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly ca...

Страница 10: ...Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correc...

Страница 11: ...onnector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input...

Страница 12: ...lation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB C...

Страница 13: ...1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting mu...

Страница 14: ...Disable Cool Air Preven tion 43 00 Super low Restrain the cold airflow with mak ing the airflow lower when starting heating operation To correspond to the ventilation set to 01 01 Follow the setting o...

Страница 15: ...unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan mo...

Отзывы: