En-3

(1)  Install the indoor unit on a place having a suf

fi

 cient strength so that it withstands 

against the weight of the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3)  Leave the space required to service the air conditioner.
(4)  Install the unit where connection to the outdoor unit (or RB unit) is easy. 
(5)  Install the unit where the connection pipe can be easily installed. 
(6)  Install the unit where the drain pipe can be easily installed.
(7)  Install the unit where noise and vibrations are not ampli

fi

 ed. 

(8)  Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the 

fi

 lter can be removed.

(9)  Do not install the unit where it will be exposed to direct sunlight.

3.2. Installation dimension

Install at least 20 mm from the ceiling.

20 mm or more

Provide a service access for inspection purposes as shown below. 
Do not place any wiring or illumination in the service space, as they will impede service.

30 or more

500 or more

500

300 or 

more

: Service access

: Service space

Indoor unit

300 or 

more

Air

Air

Unit: mm

[Top view]

3.3. Installing the unit

 WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times 
the weight of the main unit and which will not amplify sound or vibration. If the 
installation location is not strong enough, the indoor unit may fall and cause injuries.

 CAUTION

Con

fi

 rm the directions of the air intake and outlet before installing the unit.

The unit takes in air from the evaporator side, and expels it from the fan side.

3.3.1. Installing the hangers

Hanging bolt installation diagram.

1,050 mm

400 mm

155 mm

585 mm

500 mm

AIR

AIR

1,000 mm

1,080 mm

85 mm

AIR

Hanging bolt M10 
(locally purchased)

Special nut A (Large)
(Accessories)

Washer 
(locally 
purchased)

Special nut B (Small)
(Accessories)

Hanger

 CAUTION

Fasten the unit securely with special nuts A and B.

3.3.2. Leveling

Use the procedure in the following 

fi

 gure to adjust the levelness.

A

B

(Front)

Level

B

A

Level

(Side)

The side A of the unit with the drain port should be slightly lower than the opposite side B 
of the unit. The height difference between sides A and B should be from 0 to 20 mm.

3.3.3. Mounting the duct

Follow the procedure in the following 

fi

 gure to install the ducts.

862 mm

Intake port 

fl

 ange

851 mm

14 mm

324 mm

 14 mm

 Spacing between 

fl

 ange and drain pan.

Outlet port 

fl

 ange

26 mm

295 mm

 27 mm

9373870203_IM.indb   3

9373870203_IM.indb   3

2016/1/8   8:41:20

2016/1/8   8:41:20

Содержание ARXC36GBTH

Страница 1: ...6GBTH TM MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE...

Страница 2: ...service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING D...

Страница 3: ...unting position together with the customer as follows WARNING Select installation locations that can properly support the weight of the indoor unit Install the units securely so that they do not toppl...

Страница 4: ...G Install the air conditioner in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not...

Страница 5: ...pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break CAUTION To prevent people from touching the parts insid...

Страница 6: ...tion and the product 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe VP25 and connect it with adhesive polyvinyl chloride so that there is no leakage The position of the installed dr...

Страница 7: ...g the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable cur...

Страница 8: ...B units If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below fo...

Страница 9: ...bles are attached Fig B GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly ca...

Страница 10: ...Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correc...

Страница 11: ...onnector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input...

Страница 12: ...lation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB C...

Страница 13: ...1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting mu...

Страница 14: ...Disable Cool Air Preven tion 43 00 Super low Restrain the cold airflow with mak ing the airflow lower when starting heating operation To correspond to the ventilation set to 01 01 Follow the setting o...

Страница 15: ...unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan mo...

Отзывы: