En-11

6.6. Remote sensor (Optional parts) 

•   For the installation method, please refer to the INSTALLATION MANUAL of remote 

sensor.

Connection methods

• Connection terminals

Controller PCB

Remote sensor terminal 
(CN8)

• Wiring arrangement

Controller PCB

Cable clamp

Cable tie
(locally 
purchased)

•  Remove the existing connector and replace it with the remote sensor connector (ensure 

that the correct connector is used).

•   The original connector should be insulated to ensure that it does not come into contact 

with other electrical circuitry.

•  Use conduit hole when external output cable is used.

Setting for room temperature correction

When a remote sensor is connected, set the function setting of indoor unit as indicated 
below.

•  Function Number “30”: 

Set the Setting Number to “00”. (Default)

•   Function Number “31”:

Set the Setting Number to “02”.

*  Refer to “7.4. Function setting” for details about Function

Number and Setting Number.

6.7. IR receiver unit (Optional parts)

•  For the installation method, please refer to the INSTALLATION MANUAL of IR receiver 

unit.

Connection methods

• Connection terminals

Controller PCB

IR receiver unit terminal 
(CN18)

• Wiring arrangement

Core

Controller PCB

Cable clamp

Cable tie
(locally 
purchased)

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.

(1)  IU AD, REF AD SW settings .............. This section (7.1. Setting the address)
(2)  Remote controller settings ...............  Refer to the wired or wireless remote controller 

manual for detailed setting information. (Set IU 
AD, REF AD SW to 0)

(3)  Automatic address settings .............  Refer to the outdoor unit manual for detailed 

setting information. (Set IU AD, REF AD SW to 0)

 CAUTION

Be sure to turn OFF the power before performing the 

fi

 eld setting.

7.1. Setting the address

Manual address setting method

•  If the receiver unit is attached, the indoor unit address and the refrigerant circuit 

address can also be set up through the wireless remote controller.

 

CAUTION

Use an insulated screwdriver to set the DIP switches.

9373870203_IM.indb   11

9373870203_IM.indb   11

2016/1/8   8:41:21

2016/1/8   8:41:21

Содержание ARXC36GBTH

Страница 1: ...6GBTH TM MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE...

Страница 2: ...service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING D...

Страница 3: ...unting position together with the customer as follows WARNING Select installation locations that can properly support the weight of the indoor unit Install the units securely so that they do not toppl...

Страница 4: ...G Install the air conditioner in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not...

Страница 5: ...pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break CAUTION To prevent people from touching the parts insid...

Страница 6: ...tion and the product 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe VP25 and connect it with adhesive polyvinyl chloride so that there is no leakage The position of the installed dr...

Страница 7: ...g the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable cur...

Страница 8: ...B units If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below fo...

Страница 9: ...bles are attached Fig B GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly ca...

Страница 10: ...Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correc...

Страница 11: ...onnector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input...

Страница 12: ...lation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB C...

Страница 13: ...1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting mu...

Страница 14: ...Disable Cool Air Preven tion 43 00 Super low Restrain the cold airflow with mak ing the airflow lower when starting heating operation To correspond to the ventilation set to 01 01 Follow the setting o...

Страница 15: ...unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan mo...