En-6

Hose opening view

Wind the attached heat insulation 
around the hose band. Make sure the 
alignment is on top.

After installing the Drain hose, check if the drainage is smooth.

Downward gradient 
2.5-5.0mm

GOOD

PROHIBITED

Install the drain pipe

1

 

Main drain

 

On the main drain, provide 1 trap near the indoor unit.

Trap

H

2

H

1

H

1

=100 mm (Approx.)

H

2

=50 to 100 mm

Unit

Drain pipe (Main)

2

 

Safety drain

 

There is no need to provide a trap for the safety drain. 
If the safety drain is connected to the main drain, make the connection below the main 
trap.

Drain pipe (Main)

Unit

Drain pipe (Safety)

•  Make sure that drain pipe is installed without rises.
•  Do not perform air bleeding.

Rise

Air bleeding

Rise

PROHIBITED

 CAUTION

Be sure to properly insulate the drain pipes.

Make sure the drain water is properly drained.

6. ELECTRICAL WIRING

 WARNING

Electrical work must be performed in accordance with this Manual by a person certi

fi

 ed 

under the national or regional regulations. Be sure to use a dedicated circuit for the unit. 
An insuf

fi

 cient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or 

fi

 re.

Before starting work, check that power is not being supplied to the all units.

Use the included connection cables and power cables or ones specified by the 
manufacturer. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

For wiring, use the prescribed type of cables, connect them securely, making sure 
that there are no external forces of the cables applied to the terminal connections. 
Improperly connected or secured cables can cause serious accidents such as 
overheating the terminals, electric shock, or 

fi

 re.

Do not modify the power cables, use extension cables, or use any branches in the 
wiring. Improper connections, insufficient insulation, or exceeding the allowable 
current can cause electric shock or 

fi

 re.

Match the terminal board numbers and connection cable colors with those of the 
outdoor unit (or RB unit). Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or 

fi

 re.

Always fasten the outside covering of the connection cable with the cable clamp. (If 
the insulator is chafed, electric discharge may occur.)

Securely install the electrical box cover on the unit. An improperly installed electrical 
box cover can cause serious accidents such as electric shock or 

fi

 re through exposure 

to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

Install an earth leakage breaker. In addition, install the earth leakage breaker so that 
the entire AC main power supply is cut off at the same time. Otherwise, electric shock 
or 

fi

 re could result.

Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly quali

fi

 ed persons in order to avoid a hazard.

9373870203_IM.indb   6

9373870203_IM.indb   6

2016/1/8   8:41:21

2016/1/8   8:41:21

Содержание ARXC36GBTH

Страница 1: ...6GBTH TM MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE...

Страница 2: ...service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING D...

Страница 3: ...unting position together with the customer as follows WARNING Select installation locations that can properly support the weight of the indoor unit Install the units securely so that they do not toppl...

Страница 4: ...G Install the air conditioner in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not...

Страница 5: ...pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break CAUTION To prevent people from touching the parts insid...

Страница 6: ...tion and the product 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe VP25 and connect it with adhesive polyvinyl chloride so that there is no leakage The position of the installed dr...

Страница 7: ...g the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable cur...

Страница 8: ...B units If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below fo...

Страница 9: ...bles are attached Fig B GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly ca...

Страница 10: ...Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correc...

Страница 11: ...onnector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input...

Страница 12: ...lation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB C...

Страница 13: ...1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting mu...

Страница 14: ...Disable Cool Air Preven tion 43 00 Super low Restrain the cold airflow with mak ing the airflow lower when starting heating operation To correspond to the ventilation set to 01 01 Follow the setting o...

Страница 15: ...unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan mo...

Отзывы: