En-4

B. Under ceiling type

Using the installation template, drill holes for piping and suspension bolts (for holes).

Unit: in. (mm)

Installation 
template
(Accessories)

7-7/8 
(200)

Drilling position 
for suspension 
bolt

Ceiling
Wall

Drilling position for piping

35-7/16 (900)

B-1. Drilling for piping

Select piping and drain directions.

Top

Rear (Install the drain hose 
in this direction.)

Right

Hole

VIEW 

For direction, bore the oval hole shown in the above 

fi

 gure.

 

CAUTION

Install the drain hose at the rear; it should not be installed on the top or right side.

When the directions are selected, drill 3-1/8 in. (80 mm) and 1-15/16 in. (50 mm) or 
5-7/8 in. (150 mm) dia. hole on the wall so that the hole is tilted downward toward the out-
door for smooth water 

fl

 ow.

Unit: in. (mm)

Wall

1/4 (6)

Indoor side

Outdoor side 

B-2.  Drilling the holes and attaching the suspension bolts

Drill 

Φ

1 in. (25 mm) holes at the suspension bolt locations, then install the bolts.

Bolt Strength

220 to 330 lbf (980 to 1470 N)

Φ

1 (25)

Unit: in. (mm)

Ceiling panel

13/16 to 1-15/16 (20 to 50)

[If using anchor bolts]

Drill holes for anchor bolts at the locations at which you will set the suspension bolts. Note 
that anchor bolts are M10 bolts (to be obtained locally).

Anchor-Bolt Strength

220 to 330 lbf (980 to 1470 N)

M10 Anchor bolt 

(Field supply)

Ceiling

13/16 to 1-15/16
(20 to 50)

Unit: in. (mm)

B-3. Installing Brackets

Install the bracket with nuts, spring washers.

 

Bracket (Right)
(Accessories)

Bracket

Bracket (Left)
(Accessories)

Special nut A 
(Accessories)

Ceiling panel

Spring washer 
(Field supply)

M10 Nut (Field supply)

M10 Nut (Field supply)

]1

3.3. Installation the unit

 

WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times 
the weight of the main unit and which will not amplify sound or vibration. If the 
installation location is not strong enough, the indoor unit may fall and cause injuries.

3.3.1. Preparing indoor unit installation

Open the intake grille and remove the 3 screws.

Machine screw

Tapping screw

Tapping screw

Intake grille

Remark :  The main unit can be wired before the indoor unit is installed.
 

Select the most appropriate installation order.

3.3.2. Indoor unit installation
A. Floor console type 
Drilling for piping

Select piping and drain directions.
The piping and drain can be made in 3 directions as shown below.

VIEW 

Hole

For direction, bore the oval hole shown in the above 

fi

 gure.

The drain hose can be connected to either the left or right side.

Drain hose 
(Right side)

Drain hose 
(Left side)

When the directions are selected, drill a 3-15/16 in. (100 mm) dia. hole on the wall so that 
the hole is tilted downward toward the outdoor for smooth water 

fl

 ow.

When the pipe is led out from the rear, make a hole as shown in the 

fi

 gure, at the position 

shown.

Unit: in. (mm) 

1/4 (6)

3-15/16 (100)

Wall

Indoor side

Outdoor side

When installing set to wall install the accessory wall bracket at the position as shown in 
the 

fi

 gure, and mount the set to it.

Wall bracket

Unit: in. (mm)

Side of set

39 (990)

19-11/16 (500)

2-9/16

(65)

25-13/16 (655)

20-7/8 (530)

1-3/4 (45)

2-9/16 (65)

Ø1-15/16

(50)

4-15/16 (125)

3-15/16 (100)

Ø

3-15/16

(100)

9-5/8

(245)

9367701124-03_IM.indb   Sec1:4

9367701124-03_IM.indb   Sec1:4

2013-10-25   13:00:39

2013-10-25   13:00:39

Содержание ABUA12TLAV

Страница 1: ...nel only PART NO 9367701124 03 ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV Fran ais MANUEL D INSTALLATION APPAREIL INT RIEUR type sol plafonnier Pour le personnel agr uniquement Espa ol MANUAL DE INST...

Страница 2: ...the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting...

Страница 3: ...dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use ded...

Страница 4: ...use refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settl...

Страница 5: ...ccessories Special nut A Accessories Ceiling panel Spring washer Field supply M10 Nut Field supply M10 Nut Field supply 1 3 3 Installation the unit WARNING Install the air conditioner in a location wh...

Страница 6: ...48 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant pip...

Страница 7: ...iquid pipes Failure to do so may cause water leaks After checking for gas leaks insulate by wrapping insulation around the 2 parts Gas and Liquid of the indoor unit coupling using the coupler heat ins...

Страница 8: ...ctric shock or fire Before starting work check that power is not being supplied to the all units Use the included connection cables and power cables or ones specified by the manufacturer Improper conn...

Страница 9: ...37 to 90 Heat pump type indoor units Heat recovery type indoor units and RB units If the total number of units connected to the breaker exceeds 36 either add a 30mA breaker or use breakers with a grea...

Страница 10: ...emote controller cable Shielded wire no film 1 3 16 in 30 mm 1 15 16 in 50 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cabl...

Страница 11: ...nd output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of th...

Страница 12: ...rning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting...

Страница 13: ...s and the refrigerant circuit address can also be set up through the wireless remote controller Set it according to the following procedures when setting manually It can be set manually if the cover s...

Страница 14: ...er 02 Shorter Filter indicator action 13 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller...

Страница 15: ...r lamp Orange FILTER indicator lamp Red MANUAL AUTO button 7 3 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function settings It...

Страница 16: ...r plate Left 1 Join the cover plates left and mount with screws Tapping screw M4 10 mm Accessories Cover plate Left Accessories 8 4 Mount the intake grille 1 Cut the right side of the intake grille Th...

Страница 17: ...remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes...

Отзывы: