En-10

(4) Wiring
*  When there is 1 transmission cable or remote controller cable, fasten it the same way as 

shown in the 

fi

 gure with a cable tie (medium).

 

CAUTION

When switching the DIP switch (SW1), be sure to turn off the power supply to the 
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.

Cable tie (Medium)
(Accessories)

Y1,Y2,Y3:
Remote controller cable

X1, X2: 
Transmission cable

Conduit  (L1,L2(N): 
Power supply cable)

Lock nut

Earth (Ground)

DIP switch

(SW1)

For 2-wire type

Y1:Non-poler
Y2:Non-poler

Y3:Do not connect *1 

2WIRE

(Factory setting)

For 3-wire type

Y1:Red

Y2:White

Y3:Black

3WIRE

Connect the remote 
controller cable

Set the DIP switch
(SW1)

*1:  If you connect the remote controller cable to the terminal Y3, 

2-wire type remote controller does not work.

Fix the conduit with the supporters as shown below.

• 

Conduit (Power supply cable)

Supporter

Indoor unit

30 in. 

(756 mm) 

or less

54 in. 

(1,361 mm) 

or less

54 in. 

(1,361 mm) 

or less

54 in. 

(1,361 mm) 

or less

]1

6.5.  External input and external output (Optional 

parts)

 

CAUTION

Do not operate any switches other than prescribed, as it can cause the unit to operate 

improperly or malfunction.

Use an insulated screwdriver to set the DIP switches.

Controller PCB

Output terminal 
(CNB01)

(CNA03)

(CNA04)

Dry contact terminal

(CNA01)

Apply voltage terminal

(CNA02)

DIP 

switch

(SET 2)

OFF ON

SW1
SW2
SW3
SW4

(1) External input

•  Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit 

PCB CNA01 or CNA02.

•  “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

•  Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
•  A twisted pair cable (22 AWG) should be used. Maximum length of cable is 492 ft. (150 m).
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of 
terminals cannot be used simultaneously.)

 Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

Input

de

vic

e 1

Input

de

vic

e 2

Input

de

vic

e 3

Load 

resistance

Load 

resistance

Load 

resistance

*1

DC power supply
12 to 24V

connected unit

*a

*a

*a

P.C.B

CNA01

CNA03

*b

*1  Make the power supply DC12 to 24V. Select a power supply capacity with an ample 

surplus for the connected load.

Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a  The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
 

Provide a load resistance such that the current becomes DC10mA or less.

 

Select very low current use contacts (usable at DC12V, DC1mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, 
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

DC power supply 
12 to 24V

connected unit

Load 

resistance

P.C.B

P.C.B

CNA01

P.C.B

Input

de

vic

e 1

Input

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 

resistance

CNA01

CNA01

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

P.C.B

GND

Ch 1

Ch 3

*c

*c

*c

*d

Ch 2

CNA02

CNA04

connected unit

*c  Select very low current use contacts (usable at DC12V, DC1mA or less).
*d  The wiring is different from Apply voltage terminals. Be suf

fi

 ciently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 
insulate each indoor unit with relay, etc. as shown on below example.

9367701124-03_IM.indb   Sec1:10

9367701124-03_IM.indb   Sec1:10

2013-10-25   13:00:45

2013-10-25   13:00:45

Содержание ABUA12TLAV

Страница 1: ...nel only PART NO 9367701124 03 ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV Fran ais MANUEL D INSTALLATION APPAREIL INT RIEUR type sol plafonnier Pour le personnel agr uniquement Espa ol MANUAL DE INST...

Страница 2: ...the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting...

Страница 3: ...dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use ded...

Страница 4: ...use refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settl...

Страница 5: ...ccessories Special nut A Accessories Ceiling panel Spring washer Field supply M10 Nut Field supply M10 Nut Field supply 1 3 3 Installation the unit WARNING Install the air conditioner in a location wh...

Страница 6: ...48 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant pip...

Страница 7: ...iquid pipes Failure to do so may cause water leaks After checking for gas leaks insulate by wrapping insulation around the 2 parts Gas and Liquid of the indoor unit coupling using the coupler heat ins...

Страница 8: ...ctric shock or fire Before starting work check that power is not being supplied to the all units Use the included connection cables and power cables or ones specified by the manufacturer Improper conn...

Страница 9: ...37 to 90 Heat pump type indoor units Heat recovery type indoor units and RB units If the total number of units connected to the breaker exceeds 36 either add a 30mA breaker or use breakers with a grea...

Страница 10: ...emote controller cable Shielded wire no film 1 3 16 in 30 mm 1 15 16 in 50 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cabl...

Страница 11: ...nd output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of th...

Страница 12: ...rning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting...

Страница 13: ...s and the refrigerant circuit address can also be set up through the wireless remote controller Set it according to the following procedures when setting manually It can be set manually if the cover s...

Страница 14: ...er 02 Shorter Filter indicator action 13 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller...

Страница 15: ...r lamp Orange FILTER indicator lamp Red MANUAL AUTO button 7 3 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function settings It...

Страница 16: ...r plate Left 1 Join the cover plates left and mount with screws Tapping screw M4 10 mm Accessories Cover plate Left Accessories 8 4 Mount the intake grille 1 Cut the right side of the intake grille Th...

Страница 17: ...remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes...

Отзывы: