En-14

Function

Function 

number

Setting number

Default

Details

Switching 

functions for 

external inputs 

and external 

outputs termi-

nals

60

00

Mode 0

•  Set this function when connecting 

the VRF system to a ventilator, 
economizer, humidi

fi

 er, or other 

external device. 

•  The connection terminal func-

tions can be changed depending 
on the type of external device. 
For details of the connection ter-
minal functions, see the Design 
& Technical Manual. 

01

Mode 1

02

Mode 2

03

Mode 3

04

Mode 4

05

Mode 5

06

Mode 6

07

Mode 7

08

Mode 8

Control switch-

ing of external 

heaters

61

00

Auxiliary 

heater con-

trol 1

Sets the control method for the 
external heater being used. For 
details of the control method, see 
the Design & Technical Manual.

01

Auxiliary 

heater con-

trol 2

02

Heat pump 

prohibition 

control

03

Heater 

selection 

control us-

ing outdoor 

tempera-

ture 1

04

Heater 

selection 

control us-

ing outdoor 

tempera-

ture 2

Operating 

temperature 

switching 

of external 

heaters

62

00

Setting 0

•  Sets the temperature conditions 

when the external heater is ON. 

•  For the temperature conditions, 

see "Temperature conditions 
when the external heater is ON". 
For a more detailed explana-
tion, see the Design & Technical 
Manual. 

01

Setting 1

02

Setting 2

03

Setting 3

04

Setting 4

05

Setting 5

Temperature conditions when the external heater is ON 

Temperature (t) when the external heater is ON= Room temperature - set temperature 

Set value of function: 61

00

01

02

03

04

Set value of func-

tion: 62

00

t < -5.4°F (-3°C)

 -0.9°F (-0.5°C)

01

t < -3.6°F (-2°C)

 -1.8°F (-1°C)

02

t < -3.6°F (-2°C)

 -3.6°F (-2°C)

03

t < -5.4°F (-3°C)

 -5.4°F (-3°C)

04

t < -7.2°F (-4°C)

 -7.2°F (-4°C)

05

t < -9.0°F (-5°C)

 -9.0°F (-5°C)

7.3.1. Button name and function

OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)

MANUAL AUTO button

7.3.2. Checking the function settings

Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check the 
function settings. It is necessary to disconnect the power in order to return to normal op-
eration mode.

(1) Indoor unit and refrigerant address indication

Indication pattern

Indicator name

Indication pattern

Indoor unit address

Refrigerant address

OPERATION indica-
tor lamp (Green)

ON

Flash (1.0s ON/1.0s OFF)

TIMER indicator lamp (Orange)

Address: tens place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Address: ones place (0.5s ON/0.5s OFF)

•  Indoor unit address example
(Example) ADDRESS : 24

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)
FILTER 

indicator 

lamp (Red)

10 sec

1 cycle 12 sec

8 sec

ON

OFF

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

ON

•  Refrigerant address example

(Example) ADDRESS : 30

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)
FILTER 

indicator lamp 

(Red)

9 sec

1 cycle 12 sec

ON

OFF

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

ON

OFF
ON

OFF

OFF

• Setting details

Function number

Item

Setting number

01

Indoor unit address

00 to 63

02

Refrigeration address

00 to 99

For use with a remote controller, set all rotary switches to 0, and refer to “7.1. Setting the 
address” for details.
All switches are set to 0 at the factory.

(2) Others

Indication pattern

Indicator Name

Indication pattern

OPERATION indicator lamp (Green)

Function number; tens place (0.5s ON/0.5s OFF)

TIMER indicator lamp (Orange)

Function number; ones place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Setting number: (0 to 9) (0.5s ON/0.5s OFF)

(Example) Function : 31, Setting number : 2

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)

FILTER 

indicator 

lamp (Red)

11 sec

10 sec

9 sec

1 cycle 12 sec

ON

OFF

0.5s 0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s 0.5s 0.5s

ON

OFF

ON

OFF

9367701124-03_IM.indb   Sec1:14

9367701124-03_IM.indb   Sec1:14

2013-10-25   13:00:50

2013-10-25   13:00:50

Содержание ABUA12TLAV

Страница 1: ...nel only PART NO 9367701124 03 ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV Fran ais MANUEL D INSTALLATION APPAREIL INT RIEUR type sol plafonnier Pour le personnel agr uniquement Espa ol MANUAL DE INST...

Страница 2: ...the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting...

Страница 3: ...dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use ded...

Страница 4: ...use refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settl...

Страница 5: ...ccessories Special nut A Accessories Ceiling panel Spring washer Field supply M10 Nut Field supply M10 Nut Field supply 1 3 3 Installation the unit WARNING Install the air conditioner in a location wh...

Страница 6: ...48 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant pip...

Страница 7: ...iquid pipes Failure to do so may cause water leaks After checking for gas leaks insulate by wrapping insulation around the 2 parts Gas and Liquid of the indoor unit coupling using the coupler heat ins...

Страница 8: ...ctric shock or fire Before starting work check that power is not being supplied to the all units Use the included connection cables and power cables or ones specified by the manufacturer Improper conn...

Страница 9: ...37 to 90 Heat pump type indoor units Heat recovery type indoor units and RB units If the total number of units connected to the breaker exceeds 36 either add a 30mA breaker or use breakers with a grea...

Страница 10: ...emote controller cable Shielded wire no film 1 3 16 in 30 mm 1 15 16 in 50 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cabl...

Страница 11: ...nd output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of th...

Страница 12: ...rning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting...

Страница 13: ...s and the refrigerant circuit address can also be set up through the wireless remote controller Set it according to the following procedures when setting manually It can be set manually if the cover s...

Страница 14: ...er 02 Shorter Filter indicator action 13 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller...

Страница 15: ...r lamp Orange FILTER indicator lamp Red MANUAL AUTO button 7 3 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function settings It...

Страница 16: ...r plate Left 1 Join the cover plates left and mount with screws Tapping screw M4 10 mm Accessories Cover plate Left Accessories 8 4 Mount the intake grille 1 Cut the right side of the intake grille Th...

Страница 17: ...remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes...

Отзывы: