Installation Data
POSITIONING
The installation position should be selected with the following points in mind:
IM019
•
Position on a stable and even base, levelled to ensure that the compressor
operates correctly.
IM121
•
Levelling should be to +/- 5mm
as TM
•
Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections.
IM137
•
Observe airflow and maintenance clearances.
IM139
•
Pipework and electrical connections are readily accessible.
IM057
•
Where multiple units are installed, due care should be taken to avoid the
discharge air from each unit adversely affecting other units in the vicinity.
IM122
•
Within a side enclosed installation, the fan MUST be higher than the
enclosing structure.
IM142
•
Figures in brackets indicate airflow and maintenance clearances for side-enclosed
or multiple chiller applications.
as TM
•
Ensure there are no obstructions directly above the fans.
IM140
•
Allow free space above the fans to prevent air recirculation.
as TM
CAUTION
Ensure the unit is completely level and secured prior to connecting services.
new
1.2m (2.4)
1.2m (2.4)
1.2m (2.4)
1.2m (2.4)
Louvred Wall with 50%
Free Area