Installation & Maintenance Manual : 903-099 IM E 05/00
Installation Data
ELECTRICAL DATA
IM024
General
•
As standard the equipment is designed for 400V, 3 phase, 3 wire 50Hz and a
permanent 230V, 1 phase, 50Hz supply, to all relevant IEE regulations, British
standards and IEC requirements.
IM023
•
Ensure correct phase rotation.
new
CAUTION
•
A fused and isolated electrical supply of the appropriate phase, frequency and
voltage should be installed.
new
•
The control voltage to the interlocks is 24V.
Always size the low voltage interlock
and protection cabling for a maximum voltage drop of 2V.
new
CAUTION
•
Wires should be capable of carrying the maximum load current under non-
fault conditions at the stipulated voltage.
new
•
Avoid large voltage drops on cable runs, particularly low voltage wiring.
new
•
Once the connecting pipework is complete the electrical supply can be connected
by routing the cable through the appropriate casing hole and connecting the
cables, refer to the
Wiring Diagram
supplied with each unit.
new
CAUTION
A separately fused, locally isolated, permanent single phase and neutral supply is
required for the compressor sump heater, evaporator trace heating and
control circuits.
new
Interlocks & Protection
Always electrically interlock the operation of the chiller with the pump interlocks
and
water
flow switch for safety reasons.
Failure to do this will invalidate the chiller warranty.
new
CAUTION
Do not rely solely on the BMS to protect the chiller against low flow conditions. An
evaporator interlock and flow switch MUST be fitted.
new
Interconnecting Wiring
For full control panel component layout, refer to
Parts Identification
.
new
L1
ç
L2
ç
Mains Incoming Supply
L3
ç
400V/3PH/50HZ
E
ç
L4
ç
Permanent Supply
N
ç
230V/1PH/50HZ
E
ç
502
è
503
ç
Evaporator Pump Interlock 24VAC
503
è
504
ç
Evaporator Pump Water Flow Switch 24VAC
502
è
Remote ON/OFF 24VAC
505
ç
800
è
0V DC
801
è
24V DC
803
ç
Remote Setpoint Adjustment 1 to 10v dc.
573
ç
Circuit 1
Volt Free Alarm Common
574
è
Volt Free Alarm N/O
575
è
Volt Free Alarm N/C
576
ç
Circuit 2
Volt Free Alarm Common
577
è
Volt Free Alarm N/O
USC250…-12 to
USC650…-16
578
è
Volt Free Alarm N/C
E
L1
(Red)
L2
(Yellow)
L3
(Blue)
Cable Entry
Side/Base
Cable Entry
Side/Base
see TM