TurboChill™
Chillers
51
TurboChill Water Cooled Technical Manual 9216326 V1.10.0 06_2017
Compressor Maintenance
Task
Frequency
3
months
12
months
36
months
60
months
Visually check the following:
Secure/tighten as necessary
Tightness and condition of compressor mounts
Anti-vibration mounts fixings (if fitted)
Check operation of discharge non return valve
For further information refer to compressor manual which is available from Airedale on request or
the TurboCor website.
Controls
Change the compressor capacitor
Change the controller battery (may be more frequent
dependant on usage)
Electrical
Check mains power supply voltage
Check that electrical terminals are tight (tighten as needed)
Check for signs of discolouration on power cables
Check amperage are as per design
Record on maintenance records.
Maintenance
Check the following against commissioning records. Investigate and adjust as necessary.