TurboChill Water Cooled Technical Manual 9216326 V1.10.0 06_2017
(1) Based on full load conditions.
(2) Starting amps refers to the direct on line connections.
Te
ch
nic
al
TCW11XC1E1-S
TCW11XC1E1-G
TCW11XC1E1-L
Unit Data
Nominal Run Amps
(1) A
145
150
210
Maximum Start Amps
(2) A
2
2
2
Mains Supply
VAC
400V (±10%) 3PH 50Hz
Rec Mains Fuse Size
A
160
160
250
Max Mains Incoming Cable Size
mm²
70
70
185
Permanent Supply
VAC
230V (±10%) 1PH 50Hz
Rec Permanent Fuse Size
A
16
16
16
Max Permanent Incoming
Cable Size
mm²
6
6
6
Control Circuit
VAC
24V & 230V (±10%)
Evaporator
Immersion Heater Rating
W
270
270
270
Condenser
Immersion Heater Rating
W
270
270
270
Compressor
Quantity
1
1
1
Motor Rating
kW
87
92
130
Nominal Run Amps
(1) A
145
150
210
Start Amps
(2) A
2
2
2
Type Of Start
Electronic Soft Start
Technical Data
Electrical
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Overall
[dBA]
TCW11XC1E1-S
Power
69.1
70.4
68.0
68.0
75.7
73.8
63.1
58.2
78.8
Pressure @ 10m
37.3
38.7
36.2
36.3
44.0
42.1
31.4
26.4
47.0
TCW11XC1E1-G
Power
54.1
58.7
61.0
70.2
78.0
71.0
65.2
60.9
79.5
Pressure @ 10m
22.4
27.0
29.3
38.5
46.2
39.3
33.5
29.1
47.8
TCW11XC1E1-L
Power
54.1
58.7
61.0
70.2
78.0
71.0
65.2
60.9
79.5
Pressure @ 10m
22.4
27.0
29.3
38.5
46.2
39.3
33.5
29.1
47.8
Sound Data
TCW11XC1E1-S - TCW11XC1E1-G - TCW11XC1E1-L
1) dB(A) is the overall sound level, measured on the A scale.
2) All sound data measured at nominal conditions: Water in/out 12/7°C at 30°C ambient.
The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed
on a reflective base. If the equipment is placed adjacent to a reflective wall, values may vary to
those stated, typically increasing by 3dB for each side added.
IMPORTANT