TurboChill™
Chillers
50
TurboChill Water Cooled Technical Manual 9216326 V1.13.0 07_2018
System
Task
Frequency
3 months
12 months
60 months
Check the following against commissioning records:
Alarm log for unusual occurrences
Chilled water control maintains design termperatures
Chilled water flow is within design limits of zero plus 10%
Concurrently ensure chilled water pump and flow switch
operate efficiently, and that interlocks function correctly
Operation of water flow switch and pump interlock
Check pressure drop of evaporator/condenser. Clean where
appropriate.
Check glycol concentration if appropriate. Adjust as necessary.
Clean evaporator water strainer.
Leak test all refrigerant joints and visually inspect pipe and
pipework insulation.
Inspect all water connections for any leaks.
Pipe work clamps are secure.
Refrigeration
System pressure readings, suction, liquid and discharge
System temperature readings, suction, liquid and discharge
Head pressure control is maintained
Liquid level control
Check each circuit sight glass for dryness and bubbles for
indication of leaks
Pressure relief valves
F-Gas inspection
Tr
ou
ble
sh
oo
tn
g
M
ain
te
nanc
e
Maintenance
Check the following against commissioning records. Investigate and adjust as necessary.