TurboChill™
Chillers
47
TurboChill Water Cooled Technical Manual 9216326 V1.10.0 06_2017
Trou
ble
sh
oo
tin
g
C
om
mi
ssi
on
ing
●
With the unit running increase the low temperature limit to the actual supply water temperature - this will trip the
unit in a safe manner without risk of freezing the evaporator
●
Return the low temperature limit to correct value after test (this will allow the unit to operate correctly)
Pump Interlock
The pump interlock is fitted and functioning correctly.
Controls
Controller
Record on the commissioning sheet the controller serial numbers details.
●
Controller type
●
Address
●
Serial number
●
Bios
●
Boot
Also record any expansion valve driver serial numbers.
Controller Settings
The following controller settings are to be recorded on the commissioning sheet.
● Head pressure differential (Barg)
●
Minimum suction pressure (Barg)
●
Supply water set point (summer/day) (°C)
●
Supply water set point (winter/night) (°C)
●
Minimum supply water temperature (°C)