TurboChill™
Chillers
23
TurboChill Water Cooled Technical Manual 9216326 V1.10.0 06_2017
Performance Data
Measurement of Sound Data
All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated
sound intensity meter in accordance with BS EN ISO 9614 Part 1:2009. The Global sound data quoted is valid for noise
emitted in the horizontal plane in all directions.
All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO 9614 Part 1: 2009.
Sound Pressure Levels are calculated from sound power using the expanded parallelepiped method according to
BS EN ISO 11203: 2009.
Resultant performance figures obtained from test will be proven to not differ from the claimed figures by more than the
allowable deviations specified in table 7 of section VII of Eurovent RS 6/C/003-2016 (A-weighted sound power; +3dBA).”
Sound Directivity
The global sound measurements quoted in the following tables do not incorporate any directivity or denote any sound level
heard at any given position surrounding the unit, rather they represent the total sound level radiating from the unit in all
directions in the horizontal plane from source.